Description
The WAGO 885-308 stud terminal block features lateral marker slots, for DIN-rail 35 x 15 and 35 x 7.5, 3 studs, M8, 50,00 mm², gray.
Specifications
- IEC Approvals — Rated voltage (III / 3): 1000 V
- IEC Approvals — Rated impulse withstand voltage (III / 3): 8 kV
- IEC Approvals — Rated current: 150 A
- IEC Approvals — Legend (ratings): (III / 3) ≙ Overvoltage category III / Pollution degree 3
- UL Approvals — Approvals per: UL 1059
- Approvals per: CSA 22.2 No 158
- Power loss, per pole (potential): 4.725 W
- Rated current IN for power loss specification: 150 A
- Resistance value for specified, current-dependent power loss: 0 Ω
- Connection Data — Clamping units: 2
- Connection Data — Total number of potentials: 1
- Connection Data — Number of levels: 1
- Connection 1 — Connection technology: Bolt-type connection
- Connection 1 — Actuation Method: Open-end, ring, socket wrench; 13 mm
- Connection 1 — Connectable conductor materials: Copper
- Connection 1 — Clamping range: 2.5 … 50 mm² / 14 … 1/0 AWG
- Connection 1 — Type of cable lugs per DIN 46234: Cable lugs for solder-free connections; Ring type, without insulating sleeve, for copper conductors
- Connection 1 — Type of cable lugs per DIN 46235: Cable lugs for compression connections; Cover plate type for copper conductors
- Connection 1 — Thread size: M8
- Width: 22.8 mm / 0.898 inches
- Height: 67 mm / 2.638 inches
- Depth from upper-edge of DIN-rail: 56.7 mm / 2.232 inches
- Depth: 63.1 mm / 2.484 inches
- Tightening torque: 6 … 12 Nm
- Mounting type: DIN-35 rail
- Marking level: Side marking
- Color: gray
- Insulation material (main housing): Polyamide (PA66)
- Flammability class per UL94: V0
- Weight: 122.6 g
- Processing temperature: -35 … +85 °C
- Continuous operating temperature: -60 … +105 °C
- Test specification: ; Railway applications –; Rolling stock –; Electronic equipment: DIN EN 50155 (VDE 0115-200):2022-06
- Test procedure: ; Railway applications – ; Rolling stock equipment – ; Vibration and shock tests: DIN EN 61373 (VDE 0115-0106):2011-04
- Spectrum/Mounting location: Service life test, Category 1, Class A/B
- Functional test with noise-like oscillations: Test passed according to Section 8 of the standard
- Frequency: f1 = 5 Hz to f2 = 150 Hz
- Acceleration: 0.101g (highest test level used for all axes)
- Test duration per axis: 10 min.
- Test directions: X, Y and Z axes
- Monitoring of contact faults and interruptions: Passed
- Voltage drop measurement before and after each axis: Passed
- Simulated service life test through increased levels of noise-like oscillations: Test passed according to Section 9 of the standard
- Acceleration: 0.572g (highest test level used for all axes)
- Test duration per axis: 5 h
- Extended testing: Monitoring of contact faults and interruptions: Passed
- Extended testing: Voltage drop measurement before and after each axis: Passed
- Shock test: Test passed according to Section 10 of the standard
- Shock pulse form: Half sine
- Acceleration: 5g (highest test level used for all axes)
- Shock duration: 30 ms
- Number of shocks (per axis): 3 pos. und 3 neg.
- Vibration and shock stress for rolling stock equipment: Passed
Image shown is representative. Refer to the product specifications for the exact configuration.