The WAGO 883-3504 2-conductor through terminal block features 35 mm², with screw-type connection, 35,00 mm², blue.
Specifications
- IEC Approvals — Ratings per: IEC/EN 60947-7-1
- IEC Approvals — Rated voltage (III / 3): 1000 V
- IEC Approvals — Rated impulse withstand voltage (III / 3): 8 kV
- IEC Approvals — Rated current: 125 A
- IEC Approvals — Current at conductor cross-section (max.) mm²: 150 A
- IEC Approvals — Legend (ratings): (III / 3) ≙ Overvoltage category III / Pollution degree 3
- UL Approvals — Approvals per: UL 1059
- UL Approvals — Rated voltage UL (Use Group B): 600 V
- UL Approvals — Rated current UL (Use Group B): 150 A
- UL Approvals — Rated voltage UL (Use Group C): 600 V
- UL Approvals — Rated current UL (Use Group C): 150 A
- Approvals per: CSA 22.2 No 158
- Rated voltage CSA (Use Group C): 600 V
- Rated current CSA (Use Group C): 150 A
- Power loss, per pole (potential): 4.062 W
- Rated current IN for power loss specification: 125 A
- Resistance value for specified, current-dependent power loss: 0 Ω
- General information — Wiring direction: Side-entry wiring
- Connection Data — Clamping units: 2
- Connection Data — Total number of potentials: 1
- Connection Data — Number of levels: 1
- Connection Data — Number of jumper slots: 2
- Connection 1 — Connection technology: Screw connection
- Connection 1 — Actuation Method: Slot screwdriver; (6.5 x 1.2) mm blade
- Connection 1 — Connectable conductor materials: Copper; Aluminum
- Connection 1 — Connectable conductor materials (note): Terminating Aluminum Conductors; Both restrictions and application notes must be observed when terminating aluminum conductors. These instructions can be found in the WAGO Webshop under “Downloads – Documentation – Additional Information: Terminating Aluminum Conductors.”
- Connection 1 — Nominal cross-section: 35 mm²
- Connection 1 — Solid conductor: 1.5 … 50 mm² / 16 … 1/0 AWG
- Connection 1 — Stranded conductor: 1.5 … 50 mm² / 16 … 1/0 AWG
- Connection 1 — Fine-stranded conductor: 1.5 … 50 mm² / 16 … 1/0 AWG
- Connection 1 — Fine-stranded conductor; with insulated ferrule: 1.5 … 35 mm² / 16 … 2 AWG
- Connection 1 — Note (conductor cross-section): Connecting 50 mm² is only possible on a copper DIN 35 x 15 rail (2.3 mm thick).
- Connection 1 — Strip length: 18 mm / 0.71 inches
- Connection 1 — Wiring direction: Side-entry wiring
- Connection 1 — Screw thread: M6
- Width: 16.1 mm / 0.634 inches
- Height: 59 mm / 2.323 inches
- Depth from upper-edge of DIN-rail: 65.5 mm / 2.579 inches
- Tightening torque: 3.2 … 3.7 Nm
- Mounting type: DIN-35 rail; DIN-rail 35 x 7.5
- Marking level: Side marking
- Color: blue
- Insulation material (main housing): Polyamide (PA66)
- Flammability class per UL94: V0
- Weight: 58 g
- Continuous operating temperature: -35 … +105 °C
Image shown is representative. Refer to the product specifications for the exact configuration.