Description
The WAGO 857-642 timer relay module features Nominal input voltage: 24 VDC, Limiting continuous current: 6 A, Railway, Multifunction/Multitime, Yellow status indicator, Module width: 6 mm.
Specifications
- Nominal input voltage UN: 24 VDC (SELV)
- Input voltage range: ±30 %
- Nominal input current at UN: 0.5 mA
- Time range: 0.01 … 0.1 s; 0.1 … 1 s; 1 … 10 s; 10 … 100 s; 1 … 10 min; 10 … 100 min; 1 … 10 h; 10 … 100 h
- Reset time: 50 ms
- Minimum pulse length (control input): 10 ms
- Functions: On- and off-delay (with control input); On-delay and single-shot leading edge; On-delay and single-shot leading edge (with control input); Single-shot leading and trailing edge (with control input); Pulse sequence evaluation (with control input); Repeat cycle timer (pulse start); Repeat cycle timer (interval start), control input
- Number of changeover contacts: 1
- Contact material (relay): AgSnO2
- Limiting continuous current: 6 A
- Inrush current (resistive) max.: (AC) 20 A / 0.02 s
- Switching Voltage, Max.: 250 VAC
- Switching power (resistive) max.: AC 1500 VA; DC (see load limit curve)
- Utilization category: AC-15: 3 A / 250 VAC; DC-13: 2 A / DC 24 V
- Recommended minimum load: 10 V / 10 mA; 24 V / 1 mA
- Pull-in time (typ.): 15 ms
- Drop-out time (typ.): 25 ms
- Bounce time (typ.): 3.5 ms
- Electrical life (NO; resistive load; 23 °C): 50 x 10³ switching operations
- Mechanical life: 5 x 10⁶ switching operations
- Digital output (DO): UN - 1 V ; 100 mA
- Short circuit protection (load circuit): 6.3 A; Slow (T); Test based on EN 61812-1 with short-circuit current 100 ADC
- Nominal supply voltage US: 24 VDC (SELV)
- Supply voltage range: ±30 %
- Current consumption at nominal supply voltage: ≤ 17.5 mA
- Status indicator: Yellow LED
- Rated Voltage: 300 V
- Rated impulse withstand voltage: 6.4 kV
- Overvoltage category: II
- Pollution degree: 2
- Dielectric strength (control/load circuit) (AC, 1 min): 3.51 kVrms
- Dielectric strength (open contact) (AC, 1 min): 1 kVrms
- Insulation type (control/load circuit): Reinforced insulation (safe isolation)
- Insulation type (between adjacent devices of the same type): Double insulation (safe isolation)
- Insulation type (to adjacent devices of different types): Basic insulation
- Safety Information: Adjacent devices of the same type are devices of the same design (series) that are arranged next to one another on the DIN-rail with the same orientation. An end stop (249-116) must be fitted to devices of other types for compliance with the reinforced insulation requirements.
- protection rating: IP20
- Connection Data — Connection technology: Push-in CAGE CLAMP®
- Connection Data — Solid conductor: 0.34 … 2.5 mm² / 22 … 14 AWG
- Connection Data — Fine-stranded conductor: 0.34 … 2.5 mm² / 22 … 14 AWG
- Connection Data — Strip length: 9 … 10 mm / 0.35 … 0.39 inches
- Width: 6 mm / 0.236 inches
- Height: 94 mm / 3.701 inches
- Depth from upper-edge of DIN-rail: 97.8 mm / 3.85 inches
- Mounting type: DIN-35 rail
- Insulation material (main housing): Polyamide (PA66)
- Flammability class per UL94: V0
- Weight: 27 g
- Ambient temperature (operation at UN): -25 … +70 °C
- Ambient temperature (storage): -40 … +70 °C
- Processing temperature: -25 … +50 °C
- Temperature range of connection cable: ≥ (Tambient + 30 K)
- Relative humidity: 5 … 85 % (no condensation permissible)
- Operating altitude (max.): 2000 m
- Standards/specifications: EN 61373; EN 50121-3-2; UL 508; EN 61010-2-201
Image shown is representative. Refer to the product specifications for the exact configuration.