Description
Belden 3077F 003500 Fieldbus, 1 Pr #22 Str TC, PP Ins, OS, PVC Jkt, Flexible, PLTC, ITC, CM
Fieldbus, 1 Pair 22AWG (7x30) Tinned Copper, PP Insulation, Overall Beldfoil® Shield, PVC Outer Jacket, Flexible, PLTC, ITC, CM
Ordering Details
- Manufacturer Part Number: 3077F 003500
- Color: Orange
- Length: 500 ft
- Put-Up: Reel
- UPC/EAN: 612825140306
- Manufacturer Footnote: C N
Supplied as one 500 ft Reel.
Product Overview
- Suitable Applications: harsh environment digital and serial two-way communication, oil and gas extraction and refining sites, petrochemical, Profibus process automation or Foundation FieldBus process automation, extreme temperature environments, exposure to humidity/moisture, dust, and oil, remote locations long distance applications, etc.
Construction Details
- Element: Pair(s); No. of Elements: 1; Size: 22 AWG; Stranding: 7x30; Material: TC - Tinned Copper
- Element: Pair(s); Material: PP - Polypropylene; Nom. Thickness: 0.015 in (0.38 mm); Color Code: Blue & Orange
- Shield Type: Tape; Material: Bi-Laminate (Alum+Poly); Coverage: 100%; Drainwire Type: 22 AWG (7x30) TC
- Material: PVC - Polyvinyl Chloride; Nom. Thickness: 0.037 in (0.94 mm); Nom. Diameter: 0.197 in (5.00 mm)
- Overall Cable Diameter (Nominal): 0.197 in (5.00 mm)
Electrical Characteristics
- Element: Pair(s); Nom. Conductor DCR: 17.1 Ohm/1000ft (56.1 Ohm/km); Nom. Capacitance Cond-to-Shield: 44 pF/ft (140 pF/m); Max. Capacitance Unbalance: 1.2 pF/ft; Nom. Characteristic Impedence: 100 Ohm; Nom. Inductance: 0.2 µH/ft (0.66 µH/m); Nom. Velocity of Prop.: 66%; Max. Current: 2.5 Amps per Conductor
- Nom Outer Shield DCR: 11.4 Ohm/1000ft (37.4 Ohm/km)
- Element: Pair(s); Frequency [MHz]: 0.039; Nom. Insertion Loss (Attenuation) [dB/100ft]: 0.14
- UL Voltage Rating: 300 V (CM, PLTC), 150 V (ITC)
Mechanical Characteristics
- UL Temperature: 105°C; Operating: -30°C to +105°C
- Max. Pull Tension: 27 lbs (12 kg)
- Bulk Cable Weight: 18 lbs/1000ft (27 kg/km)
Standards and Compliance
- Environmental Suitability: Outdoor, Sunlight Resistance
- Flammability / Reaction to Fire: UL1685 UL Loading, IEC 60332-1-2
- CPR Compliance: CPR Euroclass: Eca
- NEC / UL Compliance: Article 725, Article 727, Article 800, CM, ITC, PLTC
- CEC / C(UL) Compliance: CM
- European Directive Compliance: EU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)
- UK Regulation Compliance: UKCA Mark
- APAC Compliance: China RoHS II (GB/T 26572-2011)
Product Notes
- Notes: CPE & Low Smoke Jacket optional.
History
- Update and Revision: Revision Number: 0.526 Revision Date: 02-20-2026
- Footnote: C - CRATE REEL PUT-UP., N - FINAL PUT-UP LENGTH MAY VARY -0% TO +10% FROM LENGTH SHOWN.