Description of Function

The relay energizes (and the LED is Red) when the monitored voltage is between the over and under voltage settings. The relay de-energizes (and the LED is Green) when the monitored voltage falls outside the over or under voltage settings for a period longer than the drop-out time delay (t), which is adjustable between 0.1-10 seconds. The relay re-energizes when the monitored voltage returns to a value between the over and under voltage settings for a period longer than the pick-up time delay, which is fixed at 0.5 seconds.

Features

  • Monitors AC single phase and DC voltages
  • Provides voltage band (window) protection
  • True RMS voltage measurement ensures more accurate sensing
  • Wide range of user-adjustable over voltage and under voltage settings
  • Adjustable time delay on drop-out of 0.1-10 seconds
  • LED indicates output relay status
  • Compact plug-in case utilizing industry standard 8 pin octal socket
  • Pilot duty rating
  • 10A output contacts

Specifications

  • Function: Voltage Band (Window)
  • Nominal Voltage: 110V DC
  • Output: 10A DPDT
  • Time Delay on Fault: 0.1-10 Sec
  • Mount: 8-Pin Socket
  • Setting Adjustment: Analog
  • Monitored Voltage: 62-138V DC
  • Dropout Voltage Setting: Adjustable % of pick-up voltage setting
  • Enclosure Style: Plug-In
  • Configuration / Contact Rating: DPDT 10A @ 240V AC / 7A @ 30V DC, 1/4HP @ 120/240V AC, C300
  • Approvals: UL Recognized for the U.S. and Canada, CE
  • Voltage Tolerance: ±50% of nominal DC voltage
  • Power Consumption: Less than 2VA
  • Voltage Settings: Pick-up (Umax): Adjustable across full range as shown in the product selection table
  • Voltage Settings: Drop-out: 75-95% of Over/Under Voltage Setting
  • Setting Accuracy: Maximum Setting (Adjustable): +5%, -0%
  • Setting Accuracy: Minimum Setting (Adjustable): +0%, -50%
  • Setting Accuracy: Fixed Voltage Setting: ±2%
  • Repeatability <1%
  • Sensing Accuracy: ±2%
  • Temperature: Operating: -28°C to 65°C (-18° to 149°F)
  • Temperature: Storage: -40°C to 85°C (-40° to 185°F)
  • Response Times: Pick-up: 0.5 seconds
  • Response Times: Drop-out (t): Adjustable 0.1-10 seconds
  • Life: Mechanical: 10,000,000 operations
  • Life: Full Load: 100,000 operations
  • Transient Protection: 2000V per IEC 61000-4-5 Level 3 (±2kV)
  • Reset: Automatic

Resources