Description
Description of Function
The relay energizes when the monitored voltage is within the set window. An excursion beyond the upper or lower setting starts the adjustable drop-out delay. If the voltage remains outside the window at the end of the delay, the relay de-energizes. The relay can pick up again once the voltage returns within the reset thresholds.
Features
- Adjustable upper and lower voltage thresholds
- LED indicators for supply power and operating status
Specifications
- Nominal monitored voltage: 120 V AC
- Adjustable upper threshold: 80–150 V AC
- Lower threshold: 30–95% of upper threshold
- Drop-out delay: Adjustable 0.1–10 seconds
- Output: 15 A SPDT at 240 V AC, B300
- Mounting: 35 mm DIN rail, 17.5 mm module
- Approvals: CE and cULus Listed
Resources