Description

Description of Function

After control voltage is applied & the sensing delay on power-up (ts) is completed, the unit will begin sensing for a fault condition. A fault will occur when the monitored AC current (I) goes above the Fault Trip Current setting & remains above the Reset level for a period longer than the adjustable time delay period (t). The LED will turn ON immediately and the relay will energize after the time delay on pick-up (t) is completed. The relay will de-energize & the LED will turn OFF when the monitored AC current goes below the Reset level.

Features

  • Monitors single phase AC current
  • Detects Overcurrent Only
  • Built-in current transformer allows easy access & multiple loops for increased sensitivity
  • Adjustable time delay on fault trip
  • LED indicates fault condition
  • 10A SPDT output contacts
  • Encapsulated for protection in harsh environments
  • Pilot Duty rating

Specifications

  • Function: AC Overcurrent
  • Control voltage: 120V AC
  • Output: 10A SPDT
  • TRIP DELAY: 0.5 – 50 Sec
  • SENSING DELAY ON POWER: 5 Sec
  • MOUNT: Two Screw Mounting
  • Setting Adjustment: Analog
  • CURRENT RANGE: 2 – 20A
  • Enclosure Style: Encapsulated
  • Configuration / Contact Rating: SPDT 10A @ 240V AC / 8A @ 28V DC , 1/4HP @ 120/240V AC, B300
  • Approvals: UL Recognized for the U.S. and Canada
  • Voltage Tolerance: +10/-15% of nominal at 50/60 Hz
  • Load (Burden): 2 VA
  • Range: 2-20A
  • Type: Toroidal, through hole wiring
  • Setting Accuracy: Min: +0%, -50%; Max: +10%, -0%
  • Maximum Allowable Current: Steady-50A Turns; 300A Inrush for 10 Seconds
  • Trip Point Hysteresis: -5% Overcurrent sensing
  • Time Delay on Reset (Relay OFF): 100ms
  • Reset Time: 400ms.
  • Life: Mechanical: 10,000,000 operations
  • Life: Full Load: 100,000 operations
  • Temperature: Operating: -28° to 65° C (-18° to 149° F)
  • Temperature: Storage: -40° to 85° C (-40° to 185° F)
  • Mounting: Surface mount with two (2) #6 screws
  • Termination: 0.25″ male quick-connect termainals