Description
Description of Function
After control voltage is applied & the sensing delay on power-up (ts) is completed, the unit will begin sensing for a fault condition. A fault will occur when the monitored AC current (I) goes above the Fault Trip Current setting & remains above the Reset level for a period longer than the adjustable time delay period (t). The LED will turn ON immediately and the relay will energize after the time delay on pick-up (t) is completed. The relay will de-energize & the LED will turn OFF when the monitored AC current goes below the Reset level.
Features
- Monitors single phase AC current
- Detects Overcurrent Only
- Built-in current transformer allows easy access & multiple loops for increased sensitivity
- Adjustable time delay on fault trip
- LED indicates fault condition
- 10A SPDT output contacts
- Encapsulated for protection in harsh environments
- Pilot Duty rating
Specifications
- Function: AC Overcurrent
- Control voltage: 120V AC
- Output: 10A SPDT
- TRIP DELAY: 0.5 – 50 Sec
- SENSING DELAY ON POWER: 5 Sec
- MOUNT: Two Screw Mounting
- Setting Adjustment: Analog
- CURRENT RANGE: 2 – 20A
- Enclosure Style: Encapsulated
- Configuration / Contact Rating: SPDT 10A @ 240V AC / 8A @ 28V DC , 1/4HP @ 120/240V AC, B300
- Approvals: UL Recognized for the U.S. and Canada
- Voltage Tolerance: +10/-15% of nominal at 50/60 Hz
- Load (Burden): 2 VA
- Range: 2-20A
- Type: Toroidal, through hole wiring
- Setting Accuracy: Min: +0%, -50%; Max: +10%, -0%
- Maximum Allowable Current: Steady-50A Turns; 300A Inrush for 10 Seconds
- Trip Point Hysteresis: -5% Overcurrent sensing
- Time Delay on Reset (Relay OFF): 100ms
- Reset Time: 400ms.
- Life: Mechanical: 10,000,000 operations
- Life: Full Load: 100,000 operations
- Temperature: Operating: -28° to 65° C (-18° to 149° F)
- Temperature: Storage: -40° to 85° C (-40° to 185° F)
- Mounting: Surface mount with two (2) #6 screws
- Termination: 0.25″ male quick-connect termainals
Resources