Description
Description of Function
The relay energizes (and the LED is Red) when the monitored voltage is above the pick-up setting for a period longer than the fixed pick-up time delay of 0.5 seconds. The relay de-energizes (and the LED is Green) when the monitored voltage is below the drop-out setting for a period longer than the drop-out time delay (t), which is adjustable from 0.1-10 second.
Features
- Monitors AC single phase and DC voltages
- True RMS voltage measurement ensures more accurate sensing
- Wide range of user-adjustable pick-up voltages
- Adjustable time delay on drop-out of 0.1-10 seconds
- LED indicates output relay status
- Pilot duty rating
- Compact plug-in case utilizing industry standard 8 pin octal socket
Specifications
- Function: Over/Undervoltage
- Nominal Voltage: 110V DC
- Output: 10A DPDT
- Time Delay on Fault: 0.1-10 Sec
- Mount: 8-Pin Socket
- Setting Adjustment: Analog
- Enclosure Style: Plug-In
- Configuration / Contact Rating: DPDT 10A @ 240V AC / 7A @ 30V DC, 1/4HP @ 120/240V AC, C300
- Approvals: UL Recognized for the U.S. and Canada
- Voltage Tolerance: ±50% of nominal DC Voltage
- Power Consumption: Less than 2VA
- Voltage Settings: Pick-up (Umax): Adjustable across full range as shown in the product selection table
- Voltage Settings: Drop-out: Adjustable from 75-95% of pick up setting
- Setting Accuracy: Maximum Setting (Adjustable): +5%, -0%
- Setting Accuracy: Minimum Setting (Adjustable): +0%, -50%
- Setting Accuracy: Fixed Voltage Setting: ±2%
- Repeatability <1%
- Sensing Accuracy: ±2%
- Temperature: Operating: -28°C to 65°C (-18° to 149°F)
- Temperature: Storage: -40°C to 85°C (-40° to 185°F)
- Life: Mechanical: 10,000,000 operations
- Life: Full Load: 100,000 operations
- Response Times: Pick-up: 0.5 seconds
- Response Times: Drop-out (t): 0.1 – 10 seconds
- Transient Protection: 2000V per IEC 61000-4-5 Level 3 (±2kV)
- Reset: Automatic
Resources