Description
Description of Function
Upon application of control voltage, the time delay relay is ready to accept a trigger. When the trigger is applied, the output remains de-energized. Upon removal of the trigger, the output is energized and the time delay (t) begins. At the end of the time delay (t), the output is de-energized unless the trigger is removed and re-applied prior to time out (before time delay (t) elapses). Continuous cycling of the trigger at a rate faster than the time delay (t) will cause the output to remain energized indefinitely.
Features
- Each unit has 16 timing ranges built-in covering 0.05 seconds-100 hours
- Selecting a range is easy using a rotary switch (no math is required or DIP switches to set)
- Universal input voltage: 24-240V AC & 12-125V DC
- Uses industry-standard 11 pin octal sockets
- 10A output contacts can handle most pilot duty & fractional HP loads
Specifications
- Function: Single Shot Falling Edge
- CONTROL VOLTAGE: 24-240V AC & 12-125V DC
- Output: 10A DPDT
- TIMING RANGE: 50 Ms – 100 Hrs
- MOUNT: 11-Pin Socket
- Setting Adjustment: Analog
- Enclosure Style: Plug-In
- Configuration / Contact Rating: DPDT 10A @ 240V AC/30V DC, 1/2HP @ 120/240V AC (N.O.),1/3HP @ 120/240V AC (N.C.), B300 & R300; AC15 & DC18
- Approvals: UL Recognized for the U.S. and Canada
- AC Operation: +10%/-15% of nominal at 50/60Hz
- DC Operation: +10%/-15% of nominal
- Load (Burden): 3 VA
- Setting Accuracy: Maximum Setting (Adjustable): +5%, -0%
- Setting Accuracy: Minimum Setting (Adjustable): +0%, -50%
- Repeat Accuracy: +0.1% or +50ms, whichever is greater
- Reset Time: 0.04 Seconds
- Start-up Time: 0.05 Seconds
- Maintain Function Time: 0.01 Seconds
- Temperature: Operating: -28° to 65° C (-18° to 149° F)
- Temperature: Storage: -40° to 85° C (-40° to 185° F)
- Life: Mechanical: 10,000,000 operations
- Life: Full Load: 100,000 operations
Resources