Description of Function

Upon initial application of control voltage, the output is energized and time delay (t1) begins. Time Delay (t1) is adjustable as a percentage of the overall cycle time (t2). At the end of the time delay (t1), the output is de-energized for the remainder of overall cycle (t2-t1). The sequence then repeats until control voltage is removed. If control voltage is removed and reapplied, the timing cycle will be reset. A setting of 100% energizes the output continuously while a setting of 0% de-energizes the output continuously.

Features

  • Industry-standard panel cutout and mounting pattern
  • No Memory
  • Onboard potentiometer for easy time delay adjustment
  • LED indicates relay status
  • 10A SPNO output
  • Terminal block makes wiring easier from top or bottom
  • Secure termination with bare wire or crimp terminals
  • Touch-safe terminal cover available – Macromatic P/N 70600
  • Mounting hardware included

Specifications

  • Function: Percentage Timer
  • Control Voltage: 120V AC
  • Output: 10A SPNO
  • Timing range: 0 – 15 Min
  • MOUNT: 4 Screw Terminal Block
  • Setting Adjustment: Analog
  • Options: No Memory
  • Enclosure Style: Panel Mount
  • Configuration / Contact Rating: SPNO 10A @ 240V AC / 7A @ 28V DC, 1/4 HP @ 120V AC
  • Approvals: CE
  • Voltage Tolerance: +10/-15% of nominal at 50/60 Hz.
  • Load (Burden): Maximum of 3 VA for all voltages.
  • Setting Accuracy: +/- 2%
  • Setting Precision: +/- 1% of total cycle time
  • Dial Resolution: Dial settings marked in 1% increments
  • Repeat Accuracy: +0.1% or +/- 0.04 seconds, whichever is greater.
  • Reset Time: 300ms
  • Start-up Time: 0.05 Seconds
  • Temperature: Operating: -28° to 65°C (-18° to 149°F)
  • Temperature: Storage: -40° to 85°C (-40° to 185°F)
  • Life: Mechanical: 10,000,000 operations
  • Life: Full Load: 100,000 operations
  • Mounting: Panel Mount with supplied hardware
  • Pressure Clamp Screw Terminals
  • #12-22 AWG Wire, Solid, Stranded Wire
  • Recommended Tightening Torque of 7 in-lbs. (12 in-lbs maximum)