Description
Description of Function
Upon initial application of control voltage, the output is energized and time delay (t1) begins. Time Delay (t1) is adjustable as a percentage of the overall cycle time (t2). At the end of the time delay (t1), the output is de-energized for the remainder of overall cycle (t2-t1). The sequence then repeats until control voltage is removed. If control voltage is removed and reapplied, the timing cycle will be reset. A setting of 100% energizes the output continuously while a setting of 0% de-energizes the output continuously.
Features
- Industry-standard panel cutout and mounting pattern
- No Memory
- Onboard potentiometer for easy time delay adjustment
- LED indicates relay status
- 10A SPNO output
- Terminal block makes wiring easier from top or bottom
- Secure termination with bare wire or crimp terminals
- Touch-safe terminal cover available – Macromatic P/N 70600
- Mounting hardware included
Specifications
- Function: Percentage Timer
- Control Voltage: 120V AC
- Output: 10A SPNO
- Timing range: 0 – 15 Min
- MOUNT: 4 Screw Terminal Block
- Setting Adjustment: Analog
- Options: No Memory
- Enclosure Style: Panel Mount
- Configuration / Contact Rating: SPNO 10A @ 240V AC / 7A @ 28V DC, 1/4 HP @ 120V AC
- Approvals: CE
- Voltage Tolerance: +10/-15% of nominal at 50/60 Hz.
- Load (Burden): Maximum of 3 VA for all voltages.
- Setting Accuracy: +/- 2%
- Setting Precision: +/- 1% of total cycle time
- Dial Resolution: Dial settings marked in 1% increments
- Repeat Accuracy: +0.1% or +/- 0.04 seconds, whichever is greater.
- Reset Time: 300ms
- Start-up Time: 0.05 Seconds
- Temperature: Operating: -28° to 65°C (-18° to 149°F)
- Temperature: Storage: -40° to 85°C (-40° to 185°F)
- Life: Mechanical: 10,000,000 operations
- Life: Full Load: 100,000 operations
- Mounting: Panel Mount with supplied hardware
- Pressure Clamp Screw Terminals
- #12-22 AWG Wire, Solid, Stranded Wire
- Recommended Tightening Torque of 7 in-lbs. (12 in-lbs maximum)
Resources