Description of Function
When the liquid level falls below the probe, a fixed 1 second time delay begins and the LED flashes Red. At the end of the time delay, the output relay energizes and the LED is Red ON. The pump is ON to fill the tank. The relay remains energized until the liquid level rises and touches the probe. The output relay de-energizes, turning off the pump, and remains de-energized and the LED is Green ON until the liquid level falls below the probe. If the container is non-conductive or insulated, an additional probe must be installed as the COM connection where it will always be submerged.
Features
- Controls level of conductive liquids in pump up (fill) applications
- Dual Probe
- Probe is pulsed with a DC voltage to prevent electroplating
- Two adjustable sensitivity ranges
- LED status indication
- Uses industry-standard 8 pin octal socket
- Pilot duty rating
Specifications
- Function/Configuration: Dual Probe Pump Up
- Control Voltage: 240V AC
- Output: 10A SPDT
- MOUNT: 8-Pin Socket
- Setting Adjustment: Analog
- Options: Crouzet & SymCom Configuration
- Sensitivity range: 1 – 250 kΩ
- Enclosure Style: Plug-in
- Configuration / Contact Rating: SPDT 10A @ 240V AC / 7A @ 28V DC, 1/4HP @ 120V AC (N.O.)
- Approvals: UL Recognized for the U.S. and Canada, CE
- Voltage Tolerance: AC Operation: +10/-15% of nominal at 50/60 Hz
- Load (Burden): 2 VA
- Probe Voltage: 5V DC Pulsed
- Pick-up: 1 Second
- Drop-out: 1 Second
- Temperature: Operating: -28° to 65° C (-18° to 149° F)
- Temperature: Storage: -40° to 85° C (-40° to 185° F)
- Life: Mechanical: 10,000,000 operations
- Life: Full Load: 100,000 operations
- Mounting: Requires industry standard 8 pin octal socket (Macromatic 70169-D or equivalent)