Description
The WAGO 870-538 3-conductor, double-deck terminal block features 6-conductor through terminal block, L, internal commoning, conductor entry with violet marking, for DIN-rail 35 x 15 and 35 x 7.5, 2.5 mm², CAGE CLAMP®, 2,50 mm², gray.
Specifications
- IEC Approvals — Ratings per: IEC/EN 60947-7-1
- IEC Approvals — Rated voltage (III / 3): 500 V
- IEC Approvals — Rated impulse withstand voltage (III / 3): 6 kV
- IEC Approvals — Rated current: 24 A
- IEC Approvals — Legend (ratings): (III / 3) ≙ Overvoltage category III / Pollution degree 3
- Power loss, per pole (potential): 0.766 W
- Rated current IN for power loss specification: 24 A
- Resistance value for specified, current-dependent power loss: 0.001 Ω
- General information — Wiring direction: Front-entry wiring
- Connection Data — Clamping units: 6
- Connection Data — Total number of potentials: 1
- Connection Data — Number of levels: 2
- Connection 1 — Connection technology: CAGE CLAMP®
- Connection 1 — Actuation Method: Operating tool
- Connection 1 — Connectable conductor materials: Copper
- Connection 1 — Solid conductor: 0.08 … 2.5 mm² / 28 … 12 AWG
- Connection 1 — Fine-stranded conductor: 0.08 … 4 mm² / 28 … 12 AWG
- Connection 1 — Fine-stranded conductor; with insulated ferrule: 0.08 … 1.5 mm² / 28 … 14 AWG
- Connection 1 — Strip length: 6 … 7 mm / 0.24 … 0.28 inches
- Connection 1 — Wiring direction: Front-entry wiring
- Width: 5 mm / 0.197 inches
- Height: 91 mm / 3.583 inches
- Depth from upper-edge of DIN-rail: 40 mm / 1.575 inches
- Potential Marking: L
- Design: horizontal type
- Mounting type: DIN-35 rail
- Marking level: Side marking
- Color: gray
- Insulation material (main housing): Polyamide (PA66)
- Flammability class per UL94: V0
- Weight: 14.2 g
- Processing temperature: -35 … +85 °C
- Continuous operating temperature: -60 … +105 °C
- Test specification: ; Railway applications –; Rolling stock –; Electronic equipment: DIN EN 50155 (VDE 0115-200):2022-06
- Test procedure: ; Railway applications – ; Rolling stock equipment – ; Vibration and shock tests: DIN EN 61373 (VDE 0115-0106):2011-04
- Spectrum/Mounting location: Service life test, Category 1, Class A/B
- Functional test with noise-like oscillations: Test passed according to Section 8 of the standard
- Frequency: f1 = 5 Hz to f2 = 150 Hz
- Acceleration: 0.101g (highest test level used for all axes)
- Test duration per axis: 10 min.
- Test directions: X, Y and Z axes
- Monitoring of contact faults and interruptions: Passed
- Voltage drop measurement before and after each axis: Passed
- Simulated service life test through increased levels of noise-like oscillations: Test passed according to Section 9 of the standard
- Acceleration: 0.572g (highest test level used for all axes)
- Test duration per axis: 5 h
- Extended testing: Monitoring of contact faults and interruptions: Passed
- Extended testing: Voltage drop measurement before and after each axis: Passed
- Shock test: Test passed according to Section 10 of the standard
- Shock pulse form: Half sine
- Acceleration: 5g (highest test level used for all axes)
- Shock duration: 30 ms
- Number of shocks (per axis): 3 pos. und 3 neg.
- Vibration and shock stress for rolling stock equipment: Passed
Image shown is representative. Refer to the product specifications for the exact configuration.