Description
The WAGO 753-652 rS-232/485 Serial Interface.
Specifications
- Signal type: RS-232; RS-422 / RS-485
- Transmission rate: 300 Bd … 115.2 kBd
- Bit transfer: RS-485/-422: ISO 8482 / DIN 66259 - 4; RS-232: EIA/TIA-232-F
- Transmission channels: 1 TxD / 1 RxD, full-duplex, half-duplex
- Line length: RS-485/-422: approx. 1000 m (max.) twisted pair, RS-232: 40 m (max.)
- Data width: 1 x 46/1 x 22/1 x 6-byte input/output (parameterizable), 2-byte control/status
- Parity: None/Odd/Even
- Number of data bits: 7/8, adjustable
- Number of stop bits: 1/2, adjustable
- Buffer: 2560-byte input / 512-byte output
- Supply voltage (system): 5 VDC; via data contacts
- Current consumption (system supply): 85 mA
- Supply voltage (field): 24 VDC; via power jumper contacts (power supply via blade contact; transmission (field side supply voltage only) via spring contact)
- Isolation: 500 V system/field
- Indicators: LED (A-H) green/yellow/red: function, transmission status, reception status, error (buffer full), RS … active, flow control active, user LED 1, user LED 0
- Number of incoming power jumper contacts: 2
- Number of outgoing power jumper contacts: 2
- Current carrying capacity (power jumper contacts): 10 A
- Connection Data — Connection technology: inputs / outputs: 8 x CAGE CLAMP®
- Connection Data — Connectable conductor materials: Copper
- Connection Data — Connection type: Inputs/Outputs
- Connection Data — Solid conductor: 0.08 … 2.5 mm² / 28 … 14 AWG
- Connection Data — Fine-stranded conductor: 0.08 … 2.5 mm² / 28 … 14 AWG
- Connection Data — Strip length: 9 … 10 mm / 0.35 … 0.39 inches
- Width: 12 mm / 0.472 inches
- Height: 100 mm / 3.937 inches
- Depth: 69 mm / 2.717 inches
- Depth from upper-edge of DIN-rail: 61.8 mm / 2.433 inches
- Mounting type: DIN-35 rail
- Pluggable connector: Pluggable
- Housing material: Polycarbonate; polyamide 6.6
- Weight: 42.1 g
- Conformity marking: CE
- Ambient temperature (operation): 0 … +55 °C
- Ambient temperature (storage): -40 … +85 °C
- Protection type: IP20
- Pollution degree: 2 per IEC 61131-2
- Operating altitude: 0 … 2000 m / 0 … 6562 ft
- Mounting position: Horizontal left, horizontal right, horizontal top, horizontal bottom, vertical top and vertical bottom
- Relative humidity (without condensation): 95 %
- Vibration resistance: 4g per IEC 60068-2-6
- Shock resistance: 15g per IEC 60068-2-27
- EMC immunity to interference: per EN 61131-2, marine applications
- EMC emission of interference: per EN 61131-2, marine applications
- Exposure to pollutants: Per IEC 60068-2-42 and IEC 60068-2-43
- Permissible pollutant concentration H2S at a relative humidity < 75%: 10 ppm
- Permissible pollutant concentration SO 2 at a relative humidity < 75%: 25 ppm
Image shown is representative. Refer to the product specifications for the exact configuration.