Description
The WAGO 753-647 dALI Multi-Master.
Specifications
- Device specification: DALI-2 Specification: DIN IEC 62386 only in conjunction with 753-620 or 787-2857 Power Supplies
- Device-specific: Current consumption from DALI bus with alternative supply via DALI bus: 10 mA
- Topology: Number of control gears/control devices (DALI): 64 control gears + 64 control devices (addressable)
- Transmission channel: 1
- Data width: 24-byte data
- Guaranteed supply current: 200 mA
- Supply current (max.): 250 mA
- Supply voltage: DALI: 18 V (external)
- Commissioning: Commissioning and programming: via WAGO-I/O-PRO V2.3 or CODESYS 3.5; Configuration: with WAGO DALI Configurator
- Supply voltage (system): 5 VDC; via data contacts
- Current consumption (system supply): 85 mA
- Isolation: 2100 VDC DALI bus/local bus
- Indicators: LED (A-H) green/yellow/red: Easy Mode, TxD, ready for operation, 1 or 2 button operation, Full Mode, RxD, voltage present, latching function
- Connection Data — Connection technology: inputs / outputs: 8 x CAGE CLAMP®
- Connection Data — Connectable conductor materials: Copper
- Connection Data — Connection type: Inputs/Outputs
- Connection Data — Solid conductor: 0.08 … 2.5 mm² / 28 … 14 AWG
- Connection Data — Fine-stranded conductor: 0.08 … 2.5 mm² / 28 … 14 AWG
- Connection Data — Strip length: 9 … 10 mm / 0.35 … 0.39 inches
- Width: 12 mm / 0.472 inches
- Height: 100 mm / 3.937 inches
- Depth: 69 mm / 2.717 inches
- Depth from upper-edge of DIN-rail: 61.8 mm / 2.433 inches
- Mounting type: DIN-35 rail
- Pluggable connector: Pluggable
- Housing material: Polycarbonate; polyamide 6.6
- Weight: 61.4 g
- Conformity marking: CE
- Ambient temperature (operation): 0 … +55 °C
- Ambient temperature (storage): -40 … +85 °C
- Protection type: IP20
- Pollution degree: 2 per IEC 61131-2
- Operating altitude: 0 … 2000 m / 0 … 6562 ft
- Mounting position: Horizontal left, horizontal right, horizontal top, horizontal bottom, vertical top and vertical bottom
- Relative humidity (without condensation): 95 %
- Vibration resistance: 4g per IEC 60068-2-6
- Shock resistance: 15g per IEC 60068-2-27
- EMC immunity to interference: per EN 61000-6-2*, *only in connection with 753-620 DC/DC Converter or 787-1007 Power Supply
- EMC emission of interference: per EN 61000-6-3*, *only in connection with 753-620 DC/DC Converter or 787-1007 Power Supply
- Exposure to pollutants: Per IEC 60068-2-42 and IEC 60068-2-43
- Permissible pollutant concentration H2S at a relative humidity < 75%: 10 ppm
- Permissible pollutant concentration SO 2 at a relative humidity < 75%: 25 ppm
Image shown is representative. Refer to the product specifications for the exact configuration.