null

WAGO 750-8100 Controller PFC100, 2 x ETHERNET, ECO

$1,097.00
SKU:
750-8100
Shipping:
Calculated at Checkout
In Stock
Available
Before Ordering

Availability and lead times may vary. Request a quote if you need to confirm availability before placing your order.


Manufacturer Information

Wago orders require a $100 combined minimum order.

Family Owned Since 1932
Nationwide Shipping Serving all 50 states
Technical Support Product selection assistance
Project Assistance Quotes and sourcing support

Description

The WAGO 750-8100 controller PFC100 features 2 x ETHERNET, ECO.

Specifications

  • Communications: Modbus (TCP, UDP); ETHERNET; EtherNet/IP Adapter; MQTT
  • ETHERNET protocols: DHCP; DNS; NTP; FTP; FTPS; SNMP; HTTP; HTTPS; SSH
  • Visualization: Web-Visu
  • Operating system: Real-time Linux 3.18 (with PREEMPT_RT patch)
  • CPU: Cortex A8; 600 MHz
  • Programming languages per IEC 61131-3: Instruction List (IL); Ladder Diagram (LD); Function Block Diagram (FBD); Continuous Function Chart (CFC); Structured Text (ST); Sequential Function Chart (SFC)
  • Programming environment: e!COCKPIT
  • Configuration options: e!COCKPIT; WAGO-I/O-CHECK; Web-Based Management
  • Transmission rate: ETHERNET: 10/100 Mbit/s
  • Transmission medium (communication/fieldbus): ETHERNET: Twisted Pair S-UTP; 100 Ω; Cat. 5; 100 m maximum cable length
  • Main memory (RAM): 256 MB
  • Internal memory (flash): 256 MB
  • Non-volatile hardware memory: 64 kbyte
  • Program memory: 10 MB (Program and data memory (dynamically distributed))
  • Data memory: 10 MB Program and data memory (dynamically distributed)
  • Non-volatile software memory: 64. kbyte
  • Type of memory card: microSD card
  • Memory Card Slot: Push-push mechanism; Cover lid (sealable)
  • Number of modules per node (max.): 250
  • Number of modules without a bus extension (max.): 64
  • Input and output process image (internal) max.: 1000 words/1000 words
  • Input and output process image (Modbus®) max.: CODESYS V3: 32000 words/32000 words
  • Drift – system clock (25 °C): 20 ppm
  • Drift – Real Time Clock (25 °C): 3 ppm
  • RTC backup time (25 °C): 7 Tage
  • Indicators: LED (SYS, RUN, I/O, USR) red/green/orange: Status system, program, local data bus, status programmable by user (can be used via CODESYS library)
  • Supply voltage (system): 24 VDC, SELV/PELV (-25 … +30 %); via wiring interface (CAGE CLAMP® connection); External fuse required: 2 A slow-blow
  • Input current (typ.) at nominal load (24 V): 300 mA
  • Total current (system supply): 700 mA
  • Isolation: 500 V system/field
  • Connection Data — Connection technology: communication/fieldbus: Modbus (TCP, UDP): 2 x RJ-45
  • Connection Data — Connection technology: system supply: 2 x CAGE CLAMP®
  • Connection Data — Connectable conductor materials: Copper
  • Connection Data — Connection type: System supply
  • Connection Data — Solid conductor: 0.08 … 1.5 mm² / 28 … 14 AWG
  • Connection Data — Fine-stranded conductor: 0.08 … 1.5 mm² / 28 … 14 AWG
  • Connection Data — Strip length: 5 … 6 mm / 0.2 … 0.24 inches
  • Connection Data — Connection technology: device configuration: 1 x Male connector; 4-pole
  • Width: 49.5 mm / 1.949 inches
  • Height: 96.8 mm / 3.811 inches
  • Depth: 71.9 mm / 2.831 inches
  • Depth from upper-edge of DIN-rail: 64.7 mm / 2.547 inches
  • Mounting type: DIN-35 rail
  • Color: light gray
  • Housing material: Polycarbonate; polyamide 6.6
  • Weight: 112 g
  • Conformity marking: CE
  • Ambient temperature (operation): 0 … +55 °C
  • Ambient temperature (storage): -25 … +85 °C
  • Protection type: IP20
  • Pollution degree: 2 per IEC 61131-2
  • Operating altitude: without temperature derating: 0 … 2000 m; with temperature derating: 2000 … 5000 m (0.5 K/100 m); 5000 m (max.)
  • Mounting position: Horizontal left, horizontal right, horizontal top, horizontal bottom, vertical top and vertical bottom
  • Relative humidity (without condensation): 95 %
  • Vibration resistance: 4g per IEC 60068-2-6
  • Shock resistance: 15g per IEC 60068-2-27
  • EMC immunity to interference: per EN 61000-6-2, marine applications
  • EMC emission of interference: per EN 61000-6-3, marine applications
  • Exposure to pollutants: Per IEC 60068-2-42 and IEC 60068-2-43
  • Permissible pollutant concentration H2S at a relative humidity < 75%: 10 ppm
  • Permissible pollutant concentration SO 2 at a relative humidity < 75%: 25 ppm
  • Pre-contractual Information: Data-Act-750-Series-Controller

Image shown is representative. Refer to the product specifications for the exact configuration.