Description
The WAGO 750-806 controller DeviceNet.
Specifications
- Communications: DeviceNet
- Visualization: none
- CPU: 16 bits
- Programming languages per IEC 61131-3: Instruction List (IL); Ladder Diagram (LD); Function Block Diagram (FBD); Continuous Function Chart (CFC); Structured Text (ST); Sequential Function Chart (SFC)
- Programming environment: WAGO-I/O-PRO V2.3
- Configuration options: EDS device description file; WAGO-I/O-CHECK
- Cycle time: < 3 ms for 1000 bit instructions/ 256 digital I/O
- Transmission rate: 500 kBd (125 kBd, 250 kBd, 500 kBd)
- Bus segment length (max.): 500 m
- Transmission medium (communication/fieldbus): Shielded Cu cable; Remote bus cable: 2 x 0.82 mm² + 2 x 1.7 mm²; Drop cable: 2 x 0.2 mm² + 2 x 0.32 mm²
- Number of fieldbus nodes on master (max.): 64
- Number of I/O points: 6,000
- Program memory: 128 KB
- Data memory: 64 KB
- Non-volatile software memory: 8 kbyte
- Memory for fieldbus input variables (max.): 512 Byte
- Memory for fieldbus output variables (max.): 512 Byte
- Number of modules per node (max.): 64
- Number of modules without a bus extension (max.): 64
- Input and output process image (fieldbus) max.: 1024 bytes/1024 bytes
- DeviceNet features: Polled I/O message connection; Strobed I/O message connection; Change of state; Cyclic message connection; UCMM using function blocks; DeviceNet master can be programmed
- Indicators: LED (OVERF) red: device error; LED (RUN) green: Device status; LED (BUS OFF) red: Network error ; LED (CONNECT) green: Network status; LED (I/O, USR) red/green/orange: Local data bus status, status programmable by user; LED (A, B) green: System power supply status, field supply
- Supply voltage (system): 24 VDC, SELV/PELV (-25 … +30 %); via wiring interface (CAGE CLAMP® connection); External fuse required: 2 A slow-blow
- Input current via DeviceNet interface at 11 V: 120 mA
- Input current (typ.) at nominal load (24 V): 500 mA
- Power supply efficiency (typ.) at nominal load (24 V): 87 %
- Current consumption (system supply): 350 mA
- Total current (system supply): 1,650 mA
- Supply voltage (field): 24 VDC, SELV/PELV (-25 … +30 %); via power jumper contacts (supply via CAGE CLAMP® connection; distribution via spring contact); External fuse required: 10 A slow-blow
- Current carrying capacity (power jumper contacts): 10 A
- Number of outgoing power jumper contacts: 3
- Isolation: 500 V system/field
- Connection Data — Connection technology: communication/fieldbus: DeviceNet: 1 x Male connector; 5-pole
- Connection Data — Connection technology: system supply: 2 x CAGE CLAMP®
- Connection Data — Connection technology: field supply: 6 x CAGE CLAMP®
- Connection Data — Connectable conductor materials: Copper
- Connection Data — Connection type: System/field supply
- Connection Data — Solid conductor: 0.08 … 2.5 mm² / 28 … 14 AWG
- Connection Data — Fine-stranded conductor: 0.08 … 2.5 mm² / 28 … 14 AWG
- Connection Data — Strip length: 8 … 9 mm / 0.31 … 0.35 inches
- Connection Data — Connection technology: device configuration: 1 x Male connector; 4-pole
- Width: 50.5 mm / 1.988 inches
- Height: 100 mm / 3.937 inches
- Depth: 71.1 mm / 2.799 inches
- Depth from upper-edge of DIN-rail: 63.9 mm / 2.516 inches
- Mounting type: DIN-35 rail
- Color: light gray
- Housing material: Polycarbonate; polyamide 6.6
- Weight: 200 g
- Conformity marking: CE
- Ambient temperature (operation): 0 … +55 °C
- Ambient temperature (storage): -25 … +85 °C
- Protection type: IP20
- Pollution degree: 2 per IEC 61131-2
- Operating altitude: without temperature derating: 0 … 2000 m; with temperature derating: 2000 … 5000 m (0.5 K/100 m); 5000 m (max.)
- Mounting position: Horizontal left, horizontal right, horizontal top, horizontal bottom, vertical top and vertical bottom
- Relative humidity (without condensation): 95 %
- Vibration resistance: 4g per IEC 60068-2-6
- Shock resistance: 15g per IEC 60068-2-27
- EMC immunity to interference: per EN 61000-6-2, marine applications
- EMC emission of interference: per EN 61000-6-4, marine applications
- Exposure to pollutants: Per IEC 60068-2-42 and IEC 60068-2-43
- Permissible pollutant concentration H2S at a relative humidity < 75%: 10 ppm
- Permissible pollutant concentration SO 2 at a relative humidity < 75%: 25 ppm
Image shown is representative. Refer to the product specifications for the exact configuration.