Description
The WAGO 750-613 system Power Supply features 24 VDC.
Specifications
- Signal type: Voltage
- Signal type (voltage): 24 VDC
- Supply voltage (system): 24 VDC, SELV/PELV (-25 … +30 %); via wiring interface (CAGE CLAMP® connection); External fuse required: 2 A slow-blow
- Input current (typ.) at nominal load (24 V): 500 mA
- Power supply efficiency (typ.) at nominal load (24 V): 90 %
- Supply voltage (field): 24 VDC, SELV/PELV (-25 … +30 %); via power jumper contacts (supply via CAGE CLAMP® connection; distribution via spring contact); External fuse required: 10 A slow-blow
- Total current (system supply): 2,000 mA
- Current carrying capacity (power jumper contacts): 10 A
- Number of outgoing power jumper contacts: 3
- Isolation: 500 V system/field
- Indicators: LED (A, B) green: operating voltage status: system, power jumper contacts
- Connection Data — Connectable conductor materials: Copper
- Connection Data — Connection type: System/field supply
- Connection Data — Solid conductor: 0.08 … 2.5 mm² / 28 … 14 AWG
- Connection Data — Fine-stranded conductor: 0.08 … 2.5 mm² / 28 … 14 AWG
- Connection Data — Strip length: 8 … 9 mm / 0.31 … 0.35 inches
- Connection Data — Connection technology: field supply: 6 x CAGE CLAMP®
- Connection Data — Connection technology: system supply: 2 x CAGE CLAMP®
- Width: 12 mm / 0.472 inches
- Height: 100 mm / 3.937 inches
- Depth: 69.8 mm / 2.748 inches
- Depth from upper-edge of DIN-rail: 62.6 mm / 2.465 inches
- Mounting type: DIN-35 rail
- Pluggable connector: fixed
- Color: light gray
- Housing material: Polycarbonate; polyamide 6.6
- Weight: 55 g
- Conformity marking: CE
- Ambient temperature (operation): 0 … +55 °C
- Ambient temperature (storage): -40 … +85 °C
- Protection type: IP20
- Pollution degree: 2 per IEC 61131-2
- Operating altitude: 0 … 2000 m / 0 … 6562 ft
- Mounting position: Horizontal left, horizontal right, horizontal top, horizontal bottom, vertical top and vertical bottom
- Relative humidity (without condensation): 95 %
- Vibration resistance: 4g per IEC 60068-2-6
- Shock resistance: 15g per IEC 60068-2-27
- EMC immunity to interference: per EN 61000-6-2, marine applications
- EMC emission of interference: per EN 61000-6-4, marine applications
- Exposure to pollutants: per IEC 60068-2-42 and IEC 60068-2-43
- Permissible pollutant concentration H2S at a relative humidity < 75%: 10 ppm
- Permissible pollutant concentration SO 2 at a relative humidity < 75%: 25 ppm
Image shown is representative. Refer to the product specifications for the exact configuration.