null
Happy Thanksgiving! We’ll be closed and

WAGO 750-538 2-channel relay output, Potential-free, 2 changeover contacts, Intrinsically safe

$625.50
SKU:
750-538
Shipping:
Calculated at Checkout
In Stock
Available
Before Ordering

Availability and lead times may vary. Request a quote if you need to confirm availability before placing your order.


Manufacturer Information

Wago orders require a $100 combined minimum order.

Family Owned Since 1932
Nationwide Shipping Serving all 50 states
Technical Support Product selection assistance
Project Assistance Quotes and sourcing support

Description

The WAGO 750-538 2-channel relay output features Potential-free, 2 changeover contacts, Intrinsically safe.

Specifications

  • Item description: 2-Channel Relay Output; Changeover contact; Potential-free
  • Number of digital outputs: 2
  • Number of Channels: 2
  • Signal type: Digital
  • Signal type (voltage): 100 VAC; 30 VDC
  • Actuator connection: 2 x (3-wire)
  • Output characteristic: potential-free
  • Output circuit design: 2 changeover contacts; Relay
  • Switching frequency (max.): 0.3 Hz
  • Load type: Resistive, inductive, lamp load
  • Switching voltage (max.): 100 VAC, 30 VDC
  • Switching current (max.): 0.5 A
  • Switching current (note): 0.5 A at 100 VAC; 1 A at 30 VDC
  • Switching voltage (min.): 0.01 V
  • Switching current (min.): 0.01 mA
  • Switching power: 50 VA / 30 W
  • Pull-in time (max.): 4 ms
  • Drop-out time (max.): 4 ms
  • Electrical switching operations (min.) (at max. resistive load): 100 x 10³ switching operations
  • Mechanical switching operations (min.) (at max. resistive load): 100 x 10⁶ switching operations
  • Intrinsically safe Ex i: Yes
  • Output data width (internal) max.: 2 Bit
  • Supply voltage (system): 5 VDC; via data contacts
  • Current consumption (system supply): 26 mA
  • Supply voltage (field): 24 VDC; (Ex i power supply: Uo = max. 26.8 V); via power jumper contacts (supply via blade contact; distribution via spring contact)
  • Current consumption, field supply (module with no external load): 24 mA
  • Power consumption Pmax.: 0.8 W
  • Power loss Pl: 0.8 W
  • Isolation: 300 VAC system/supply
  • Number of incoming power jumper contacts: 2
  • Number of outgoing power jumper contacts: 2
  • Current carrying capacity (power jumper contacts): 1 A
  • Indicators: LED (A, E) green: Status relay 1, relay 2
  • Identification: ATEX: II 3 (1) G Ex ec [ia Ga] IIC T4 Gc; II (1) D [Ex ia Da] IIIC; I (M1) [Ex ia Ma] I; IECEx/INMETRO: Ex ec [ia Ga] IIC T4 Gc; [Ex ia Da] IIIC; [Ex ia Ma] I; cULus (Zone classified): Cl I Zn 2 AEx nA [ia Ga] IIC T4 Gc; Cl I Zn 2 AEx nA [ia IIIC] IIC T4 Gc; Ex nA [ia Ga] IIC T4 Gc X; Ex nA [ia IIIC] IIC T4 Gc X; cULus (Devision classified): Class I, Div. 2, Group A B C D, T4
  • Ex standard: EN IEC 60079-0, -7, -11
  • Safety-relevant data (circuit): Relay output: Ui = 30 VDC; Ii = 1 A; Pi = 30 W; Ui = 100 VAC; Ii = 0.5 A; Pi = 50 VA; Li = negligibly small; Ci = negligibly small.Both maximum switching current and voltage must comply with EN 60079-11.
  • Connection Data — Connection technology: inputs / outputs: 6 x CAGE CLAMP®
  • Connection Data — Connectable conductor materials: Copper
  • Connection Data — Connection type: Inputs/outputs
  • Connection Data — Solid conductor: 0.08 … 2.5 mm² / 28 … 14 AWG
  • Connection Data — Fine-stranded conductor: 0.08 … 2.5 mm² / 28 … 14 AWG
  • Connection Data — Strip length: 8 … 9 mm / 0.31 … 0.35 inches
  • Width: 12 mm / 0.472 inches
  • Height: 100 mm / 3.937 inches
  • Depth: 67.8 mm / 2.669 inches
  • Depth from upper-edge of DIN-rail: 60.6 mm / 2.386 inches
  • Mounting type: DIN-35 rail
  • Color: blue
  • Housing material: Polycarbonate; polyamide 6.6
  • Weight: 49.1 g
  • Conformity marking: CE
  • Ambient temperature (operation): 0 … +55 °C
  • Ambient temperature (storage): -25 … +85 °C
  • Protection type: IP20
  • Pollution degree: 2 per IEC 61131-2
  • Operating altitude: 0 … 2000 m / 0 … 6562 ft
  • Mounting position: Horizontal left, horizontal right, horizontal top, horizontal bottom, vertical top and vertical bottom
  • Relative humidity (without condensation): 95 %
  • Vibration resistance: 4g per IEC 60068-2-6
  • Shock resistance: 15g per IEC 60068-2-27
  • EMC immunity to interference: per EN 61000-6-2, marine applications
  • EMC emission of interference: per EN 61000-6-3, marine applications
  • Exposure to pollutants: per IEC 60068-2-42 and IEC 60068-2-43
  • Permissible pollutant concentration H2S at a relative humidity < 75%: 10 ppm
  • Permissible pollutant concentration SO 2 at a relative humidity < 75%: 25 ppm

Image shown is representative. Refer to the product specifications for the exact configuration.