null

WAGO 750-495 3-Phase Power Measurement, 690 VAC, 1 A

$751.30
SKU:
750-495
Shipping:
Calculated at Checkout
In Stock
Available
Before Ordering

Availability and lead times may vary. Request a quote if you need to confirm availability before placing your order.


Manufacturer Information

Wago orders require a $100 combined minimum order.

Family Owned Since 1932
Nationwide Shipping Serving all 50 states
Technical Support Product selection assistance
Project Assistance Quotes and sourcing support

Description

The WAGO 750-495 3-Phase Power Measurement features 690 VAC, 1 A.

Specifications

  • Number of measurement inputs: 7 (3 voltage measurement inputs, 4 differential current measurement inputs)
  • Signal type: Power measurement
  • Signal form: Sinusoidal signals (taking the cutoff frequency into account)
  • Resolution [bit]: 24 Bit
  • Data width: 2 x 128-bit data; 2 x 64-bit control/status
  • Voltage path input resistance (typ.): 1429 kΩ
  • Current path input resistance (typ.): 22 mΩ
  • Reference for measurement error: AC current/voltage
  • Measurement error, reference temperature: 23 °C
  • Measurement error, deviation max (upper-range value) ≤±: 0.5 %
  • Measurement current (max.): 1 A
  • Measurement cycle time: Adjustable for arithmetic mean value, Min_Max_Values
  • Frequency range (mains frequency): 50/60 Hz
  • Frequency range (harmonics analysis): 0 … 3300 Hz
  • Limit frequency: 15.9 kHz
  • Permissible common mains supply systems: Three-phase, four-wire system: max. 277/480 VAC; Three-phase, three-wire system: max. 600 VAC (UL)
  • Note on common mains supply systems: ULL up to 690°V is possible under special conditions (see manual).
  • Upper-range value for the measurement accuracy: 400/690 V
  • Calculated values: Line-to-line voltage, power output, energy, power factors, mains frequency, harmonic analysis (up to the 41st harmonic), THD
  • Measurement method: True RMS measurement
  • Supply voltage (system): 5 VDC; via data contacts
  • Current consumption (system supply): 100 mA
  • Indicators: LED (A) green: Communication; LED (B-G) red: Error L1, Override in Current Measurement Path (display), Undervoltage in Voltage Measurement Path (display), Error L2, Error L3, Override in Voltage Measurement Path (display); LED (H) yellow: Interchange in Phase Sequence L1-L2-L3
  • Measurement category per EN/UL 61010-2-030: CAT III
  • Test voltage: 3.51 kVAC, 50/60 Hz, 1 min.
  • Rated impulse withstand voltage: System/field side: 5.0 kV (EN 60870-2-1 / Class VW3) 6.4 kV (EN/UL 61010-1)
  • System voltage: ≤ 300 V
  • Note on system voltage: The system voltage corresponds to the line-to-neutral voltage derived from conventional mains power supply systems.
  • Overvoltage category: III
  • Insulation type: Reinforced insulation
  • System voltage: ≤ 600 V
  • Note on system voltage: To ensure safe insulation, the module's N connector must not be connected. The system voltage corresponds to the line conductor/neutral conductor voltage, which was derived from standard power supply systems
  • Insulation type: Double isolation (basic isolation and supplementary isolation by impedance/current measurement transformer) Safe isolation from the adjacent SELV/PELV modules must be ensured. The product manual contains the types of isolation to adjacent modules in section “Isolation to Adjacent I/O Modules per EN/UL 61010 2-201.” Without double or reinforced isolation, the 750-495/000-00x Power Measurement Module must not be placed directly next to SELV/PELV modules. Under such conditions, the 750-616 Distance Module must be used.
  • Connection Data — Connection technology: inputs / outputs: 12 x CAGE CLAMP®
  • Connection Data — Connectable conductor materials: Copper
  • Connection Data — Connection type: Inputs/outputs
  • Connection Data — Solid conductor: 0.08 … 2.5 mm² / 28 … 14 AWG
  • Connection Data — Fine-stranded conductor: 0.08 … 2.5 mm² / 28 … 14 AWG
  • Connection Data — Strip length: 8 … 9 mm / 0.31 … 0.35 inches
  • Connection Data — Note (conductor cross-section): Solid conductor: 20 … 14 AWG (UL); Fine-stranded conductor: 20 … 16 AWG (UL) These values refer exclusively to the mechanical connection capacity of the clamping points. When the applications/devices are operated in locations covered by UL, only solid conductor with 20 … 14 AWG and fine-stranded conductor with 20 … 16 AWG are permitted.
  • Width: 24 mm / 0.945 inches
  • Height: 100 mm / 3.937 inches
  • Depth: 67.8 mm / 2.669 inches
  • Depth from upper-edge of DIN-rail: 60.6 mm / 2.386 inches
  • Mounting type: DIN-35 rail
  • Color: light gray
  • Housing material: Polycarbonate; polyamide 6.6
  • Weight: 90.7 g
  • Conformity marking: CE
  • Ambient temperature (operation): 0 … +55 °C
  • Ambient temperature (storage): -40 … +85 °C
  • Protection type: IP20
  • Pollution degree: 2 per EN 60664-1
  • Operating altitude: 0 … 2000 m / 0 … 6562 ft
  • Mounting position: Horizontal left, horizontal up, vertical top and vertical bottom
  • Relative humidity (without condensation): 95 %
  • Vibration resistance: 4g per IEC 60068-2-6
  • Shock resistance: 15g per IEC 60068-2-27
  • EMC immunity to interference: per EN 61000-6-2
  • EMC emission of interference: per EN 61000-6-3
  • Exposure to pollutants: per IEC 60068-2-42 and IEC 60068-2-43
  • Permissible pollutant concentration H2S at a relative humidity < 75%: 10 ppm
  • Permissible pollutant concentration SO 2 at a relative humidity < 75%: 25 ppm

Image shown is representative. Refer to the product specifications for the exact configuration.