Description
The WAGO 750-489 4-channel analog input features RTD/TC/Strain Gauge, 16 bits, Diagnostics, Intrinsically safe.
Specifications
- Item description: 4-Channel Analog Input; RTD/TC
- Number of analog inputs: 4
- Number of Channels: 4
- Signal type: Potentiometer positions; Thermocouple; Resistive temperature device; Resistors; mV encoder
- Signal type (configurable): Yes
- Sensor connection: 4 x (2-wire, 3-wire, 4-wire)
- Measurement range: RTDs: Pt100, Pt200, Pt500, Pt1000, Ni100, Ni120, Ni200, Ni500, Ni1000, Ni1000-TK5000; Resistances: 250 Ω, 500 Ω, 1 kΩ, 2 kΩ, 4 kΩ, PTC; Potentiometer setting: 0 … 100 %; Thermocouples: Type B; Type C; Type E; Type J; Type K; Type N; Type R, S; Type T; mV sensors: ±30 mV; ±60 mV; ±120 mV; ±250 mV; ±500 mV; ±1,000 mV; ±2,000 mV; PTC thermistor; Resistor bridges (strain gauges)
- Resolution (over entire range): 0.1 K of full scale value; 0.01 K of full scale value (limited to -50 … +150 °C)
- Conversion time: ≥10 ms/2 wires (per channel)*;≥20 ms/3 wires, 4 wires (per channel)*;*for RTD/R; TC/U conversion time depends on module setting
- Reference for measurement error: at 0 ≤ TA ≤ 55 °C
- Measurement error, reference temperature: 25 °C
- Measurement error, deviation max (upper-range value) ≤±: ±0.2 %
- Reference for measurement / output error: during user calibration
- Measurement error, deviation max (upper-range value) ≤±: ±0.05 %
- Temperature error max. (upper-range value) ≤±: ±0.001 %/K
- Cold junction compensation: integrated
- Intrinsically safe Ex i: Yes
- Data width: 4 x 16-bit data; 4 x 8-bit control/status (optional)
- Supply voltage (system): 5 VDC; via data contacts
- Current consumption (system supply): 50 mA
- Supply voltage (field): 24 VDC; (Ex i power supply: Uo = max. 26.8 V); via power jumper contacts (supply via blade contact; distribution via spring contact)
- Current consumption, field supply (module with no external load): 50 mA
- Power consumption Pmax.: 1.6 W (RTD/TC operation)
- Power loss Pl: 1.6 W (RTD/TC operation)
- Isolation: 300 VAC system/supply; 1200 VDC system/supply/channel
- Number of incoming power jumper contacts: 2
- Number of outgoing power jumper contacts: 2
- Indicators: LED (A, C, E, G) green: Function AI 1 … AI 4; LED (B, D, F, H) red: Error AI 1 … AI 4
- Identification: ATEX: II 3 (1) G Ex ec [ia Ga] IIC T4 Gc; II (1) D [Ex ia Da] IIIC; I (M1) [Ex ia Ma] I; IECEx/INMETRO: Ex ec [ia Ga] IIC T4 Gc; [Ex ia Da] IIIC; [Ex ia Ma] I; cULus (Devision classified): Class I, Div. 2, Group A B C D, T4
- Ex standard: EN IEC 60079-0, -7, -11
- Safety-relevant data (circuit): Uo = 4 V; Io = 21.45 mA; Po = 21.45 mW; linear characteristic
- Reactances Ex ia IIC: Lo = 0.08 H; Co = 100 µF
- Reactances Ex ia IIB: Lo = 0.31 H; Co = 1000 µF
- Reactances Ex ia IIA: Lo = 0.62 H; Co = 1000 μF
- Reactances Ex ia I: Lo = 1.01 H; Co = 1000 µF
- Reactances (note): Reactances, if the internal inductance Li or capacitance Ci (without cable) of the connected device is ≤1% of the specified values.The specified values apply to the worst case in strain gauge operation; see the manual for values for other operating modes.
- Connection Data — Connection technology: inputs / outputs: 16 x CAGE CLAMP®
- Connection Data — Connectable conductor materials: Copper
- Connection Data — Connection type: Inputs/outputs
- Connection Data — Solid conductor: 0.08 … 2.5 mm² / 28 … 14 AWG
- Connection Data — Fine-stranded conductor: 0.08 … 2.5 mm² / 28 … 14 AWG
- Connection Data — Strip length: 8 … 9 mm / 0.31 … 0.35 inches
- Width: 24 mm / 0.945 inches
- Height: 100 mm / 3.937 inches
- Depth: 67.8 mm / 2.669 inches
- Depth from upper-edge of DIN-rail: 60.6 mm / 2.386 inches
- Mounting type: DIN-35 rail
- Housing material: Polycarbonate; polyamide 6.6
- Weight: 99.3 g
- Conformity marking: CE
- Ambient temperature (operation): 0 … +55 °C
- Ambient temperature (storage): -25 … +85 °C
- Protection type: IP20
- Pollution degree: 2 per IEC 61131-2
- Operating altitude: 0 … 2000 m / 0 … 6562 ft
- Mounting position: Horizontal left, horizontal right, horizontal top, horizontal bottom, vertical top and vertical bottom
- Relative humidity (without condensation): 95 %
- Vibration resistance: 4g per IEC 60068-2-6
- Shock resistance: 15g per IEC 60068-2-27
- EMC immunity to interference: per EN 61000-6-2, marine applications
- EMC emission of interference: per EN 61000-6-3, marine applications
- Exposure to pollutants: per IEC 60068-2-42 and IEC 60068-2-43
Image shown is representative. Refer to the product specifications for the exact configuration.