Description
The WAGO 750-424 2-channel digital input features Intruder detection.
Specifications
- Number of digital inputs: 2
- Number of Channels: 2
- Signal type: Current loop (intruder detection)
- Sensor connection: 2 x (2-wire)
- Specific sensor properties: Alarm contact: R1 = 1.5 kΩ (±5 %); R2 = 2.2 kΩ (±5 %); Conductor resistance (R wire): 200 Ω (max.)
- Output current per channel: 0.001 A
- Sensor supply: 24 VDC
- Input data width (internal) max.: 4 Bit
- Data width: 4-bit input: 2-bit data, 2-bit error (short circuit/wire break)
- Supply voltage (system): 5 VDC; via data contacts
- Current consumption (system supply): 6 mA
- Supply voltage (field): 24 VDC (-25 … +30 %); via power jumper contacts (power supply via blade contact; transmission (field side supply voltage only) via spring contact)
- Current consumption, field supply (module with no external load): 16 mA
- Isolation: 500 V system/field
- Indicators: LED (A, C) green: Status DI 1, DI 2; LED (B, D) red: Error DI 1, DI 2
- Number of incoming power jumper contacts: 3
- Number of outgoing power jumper contacts: 3
- Current carrying capacity (power jumper contacts): 10 A
- Connection Data — Connection technology: inputs / outputs: 8 x CAGE CLAMP® (inputs)
- Connection Data — Connectable conductor materials: Copper
- Connection Data — Connection type: Input
- Connection Data — Solid conductor: 0.08 … 2.5 mm² / 28 … 14 AWG
- Connection Data — Fine-stranded conductor: 0.08 … 2.5 mm² / 28 … 14 AWG
- Connection Data — Strip length: 8 … 9 mm / 0.31 … 0.35 inches
- Width: 12 mm / 0.472 inches
- Height: 100 mm / 3.937 inches
- Depth: 69.8 mm / 2.748 inches
- Depth from upper-edge of DIN-rail: 62.6 mm / 2.465 inches
- Mounting type: DIN-35 rail
- Pluggable connector: fixed
- Color: light gray
- Housing material: Polycarbonate; polyamide 6.6
- Weight: 58 g
- Conformity marking: CE
- Ambient temperature (operation): 0 … +55 °C
- Ambient temperature (storage): -40 … +85 °C
- Protection type: IP20
- Pollution degree: 2 per IEC 61131-2
- Operating altitude: 0 … 2000 m / 0 … 6562 ft
- Mounting position: Horizontal left, horizontal right, horizontal top, horizontal bottom, vertical top and vertical bottom
- Relative humidity (without condensation): 95 %
- Vibration resistance: 4g per IEC 60068-2-6
- Shock resistance: 15g per IEC 60068-2-27
- EMC immunity to interference: per EN 61000-6-2, marine applications
- EMC emission of interference: per EN 61000-6-4, marine applications
- Exposure to pollutants: per IEC 60068-2-42 and IEC 60068-2-43
- Permissible pollutant concentration H2S at a relative humidity < 75%: 10 ppm
- Permissible pollutant concentration SO 2 at a relative humidity < 75%: 25 ppm
Image shown is representative. Refer to the product specifications for the exact configuration.