Description
The WAGO 286-661 current flow monitoring module features AC currents, light gray.
Specifications
- Input signal (A): AC 0 … 6 A
- Input voltage (max.): 250 VAC
- Frequency range: 50 Hz
- Voltage drop: 10 … 100 mV
- Response threshold: 80 mA
- Response time: 40 ms
- Nominal supply voltage US: 24 VDC
- Supply voltage range: ±10 %
- Current consumption at nominal supply voltage: ≤ 22 mA (+ IDO)
- Switching voltage (DO) max.: Supply voltage applied
- Continuous current (DO) max.: 50 mA (DC)
- Status indicator: Green LED; Output: 0 V (operation; current > 80 mA); Red LED; Output: 24 VDC (current flow interruption; current < 80 mA)
- Rated Voltage: 250 V
- Rated impulse withstand voltage: 3.8 kV
- Overvoltage category: II
- Pollution degree: 2
- Dielectric strength, input/output (AC, 1 min): 2.2 kVeff
- Insulation type: Basic insulation
- Insulation type (between adjacent devices of the same type): Double insulation (safe isolation)
- Insulation type (to adjacent devices of different types): Basic insulation
- protection rating: IP20
- Width: 20 mm / 0.787 inches
- Height: 52 mm / 2.047 inches
- Depth from upper-edge of DIN-rail: 82.5 mm / 3.25 inches
- Mounting type: Pluggable module for receptacle terminal blocks
- Housing design: Plug for carrier terminal blocks
- Color: light gray
- Weight: 46.6 g
- Ambient temperature (operation): -25 … +40 °C
- Ambient temperature (storage): -40 … +70 °C
- Temperature range of connection cable: ≥ (Tambient + 30 K)
- Relative humidity: 5 … 95 % (no condensation permissible)
- Operating altitude (max.): 2000 m
- Main product function: Current flow monitoring module
- Product type: Specialty electronics
- Series: 286
Image shown is representative. Refer to the product specifications for the exact configuration.