Description
The WAGO 2857-569 single-Phase Power Signal Conditioner features Current and voltage input signal, Current and voltage output signal, Digital output, Configuration via software, Supply voltage: 24 VDC.
Specifications
- Configuration options: WAGO Interface Configuration Software
- Input signal type: Voltage; Current
- Input signal (voltage): 500 V AC/DC (IN 2.1; per EN 61010-1); 300 V AC/DC (IN 2.1; per UL 61010-1); 250 V AC/DC (IN 2.2); 30 V AC/DC (IN 2.3)
- Input signal (current): 1 A AC/DC (IN 3.1); 5 A AC/DC (IN 3.2); 8 A AC/DC (IN 3.3)
- Frequency range: 15 … 400 Hz
- Input current (max.): 1.2 × IN (≤ 60 °C); 1 × IN (60 … 70 °C)
- Input voltage (max.): 1.2 × UN
- Response threshold (voltage): 500 mVAC / 600 mVDC (IN 2.1); 50 mVAC / 500 mVDC (IN 2.2); 20 mVAC / 100 mVDC (IN 2.3)
- Response threshold (current): 1.5 mAAC / 7.5 mADC (IN 3.1); 3 mAAC / 10 mADC (IN 3.2); 7.5 mAAC / 12 mADC (IN 3.3)
- Resolution (voltage): 50 mV (IN 2.1); 30 mV (IN 2.2); 5 mV (IN 2.3)
- Resolution (current): 1 mA (for all measurement ranges)
- Output signal type: Current; Voltage
- Output signal (voltage): ±12 V (SELV)
- Output signal (current): ±24 mA (SELV)
- Load impedance (voltage output): ≥ 2 kΩ
- Load impedance (current output): ≤ 600 Ω
- Switching voltage (DO) max.: Applied supply voltage - 0.3 V
- Continuous current (DO) max.: 100 mA (no internal restriction)
- Number of switching thresholds (DO): 2 (max.)
- Configurable rise/fall delay time (DO): 0 … 60 s (via software)
- Configurable functions (DO): Threshold Value Switch; Disabled; US/GND switching; Threshold value switch; Frequency generator; Pulse output (S0 interface)
- Setting range (frequency generator): 0.3 … 100 Hz
- Setting range (pulse output): 1000 … 1 pulses/kW(h)
- Number of changeover contacts: 1
- Switching Voltage, Max.: 250 VAC
- Dielectric strength (open contact) (AC, 1 min): 1 kVrms
- Number of switching thresholds (relay): 1 or 2 (adjustable)
- Configurable rise/fall delay time (relay): 0 … 60 s (via software)
- Measurement method: True RMS measurement (TRMS)
- Measured variables (calculated): Active power; Apparent power; Reactive power; Mains frequency; Phase angle
- Limit frequency: 2 kHz
- Software filter (adjustable): Filter level: 1 … 30
- Step response (max.): 350 ms (for default settings)
- Transmission error (max.): ≤ 0.5 % for current and voltage (of the full scale value)
- Power supply type: 24 VDC
- Nominal supply voltage US: 24 VDC (SELV)
- Supply voltage range: ±30 %
- Current consumption at nominal supply voltage: ≤ 70 mA (+ IDO)
- Rated Voltage: 600 V; 300 V (UL)
- Measurement category per EN/UL 61010-2-030: CAT III (input)
- Note on insulation parameters: The digital output (DO) operates at the supply potential. The service interface operates at the potential of the analog output.
- protection rating: IP20
- Test voltage (input IN 2.1/relay output; per EN 61010-1): 5.4 kVAC ; 50 Hz; 5 s; 3.6 kVAC; 50 Hz; 1 min
- Test voltage (input IN 2.1/relay output; per UL 61010-1): 3.51 kVAC; 60 Hz; 1 min
- Test voltage (input/supply and analog output/relay output): 3.51 kVAC; 50 … 60 Hz; 1 min
- Test voltage (supply/analog output): 3.6 kVAC; 50 … 60 Hz; 1 min
- Overvoltage category: III
- Pollution degree: 2
- Insulation type (input/supply and analog output/relay output): Reinforced insulation (safe isolation)
- Insulation type (input IN 2.1/relay output): Reinforced insulation (safe isolation)
- Insulation type (input/supply and analog output/relay output): Requirement: The N (GND 1) input must not be hazardous when active.; Double insulation (impedance and basic insulation); Requirement: The N (GND 1) input is dangerous when active!
- Connection Data — Connection technology: Push-in CAGE CLAMP®
- Connection Data — WAGO connector: picoMAX® 5.0
- Connection Data — Solid conductor: 0.2 … 2.5 mm² / 24 … 12 AWG
- Connection Data — Fine-stranded conductor: 0.2 … 2.5 mm² / 24 … 12 AWG
- Connection Data — Strip length: 9 … 10 mm / 0.35 … 0.39 inches
- Width: 22.5 mm / 0.886 inches
- Height: 110 mm / 4.331 inches
- Depth from upper-edge of DIN-rail: 107 mm / 4.213 inches
- Mounting type: DIN-35 rail
- Weight: 128.7 g
- Ambient temperature (operation): -40 … +70 °C
- Ambient temperature (storage): -40 … +85 °C
- Temperature range of connection cable: ≥ (Tambient + 25 K)
- Temperature range of the connection cable (UL): 95 °C
- Relative humidity: 5 … 85 % (non-condensing)
- Operating altitude (max.): 2000 m
- Conformity marking: CE
- EMC immunity to interference: EN 61000-6-2; EN 61326-2-3
- EMC emission of interference: EN 61000-6-3; EN 61326-2-3
- Standards/specifications: EN 61010-1; UL 61010-1; UL 61010-2-201
Image shown is representative. Refer to the product specifications for the exact configuration.