Description
The WAGO 2857-533 jUMPFLEX® signal conditioner features RTD threshold value switch, with picoMAX® connector, configurable.
Specifications
- Configuration options: DIP switch; WAGO Interface Configuration Software
- Input signal type: Potentiometer; Resistance; RTD sensors; Potentiometers; Resistor
- Sensor types (RTD): Pt100; Pt200; Pt500; Pt1000; Pt5000; Pt10000; Pt10 … Pt20000
- Sensor connection: 2-wire; 3-wire; 4-wire; differential
- Sensor power supply (RTD) max.: ≤ 0.5 mA
- Temperature measurement range (RTD): -200 … +850 °C
- Input range (resistor): 0 … 100 kΩ
- Input range (potentiometer): 0 … 100 kΩ
- Switching voltage (DO) max.: Applied supply voltage - 0.3 V
- Continuous current (DO) max.: 100 mA (no internal restriction)
- Number of switching thresholds (DO): 1 or 2 (adjustable)
- Configurable rise/fall delay time (DO): 0 … 60 s (via software)
- Dielectric strength (open contact) (AC, 1 min): 1 kVeff
- Number of make/switch-on contacts: 1
- Contact material (relay): AgNi + Au
- Switching Voltage, Max.: 250 VAC
- Dielectric strength (open contact) (AC, 1 min): 1 kVrms
- Pull-in time (typ.): 8 ms
- Drop-out time (typ.): 4 ms
- Bounce time (typ.): 8 ms
- Number of switching thresholds (relay): 1 or 2 (adjustable)
- Configurable rise/fall delay time (relay): 0 … 60 s (via software)
- Continuous current (max.): 6 A
- Software filter (adjustable): Moving average value (filter level: 30)
- Hysteresis: Adjustable via DIP switch or software
- Step response (typ.): 60 ms (2-wire); 360 ms (3-wire); 540 ms (4-wire); 360 ms (potentiometer)
- Transmission error (max.): ± 1 K
- Temperature coefficient: ≤ 0.01 %/K
- Power supply type: 24 VDC
- Nominal supply voltage US: 24 VDC (SELV)
- Supply voltage range: ±30 %
- Current consumption at nominal supply voltage: ≤ 40 mA (+ IDO)
- Rated Voltage: 300 V
- Rated voltage of the measurement circuit connections per EN 61010-2-030: 300 VAC
- Measurement category per EN/UL 61010-2-030: CAT II (input)
- Note on insulation parameters: Temperature sensors must not be used in hazardous circuits unless the external temperature sensors used provide basic insulation in accordance with EN 61010-1 (300 VAC; Overvoltage Category II; Pollution Degree 2). The digital output (DO) operates at the supply potential.
- protection rating: IP20
- Test voltage (input/relay output/supply): 4 kVAC; 60 Hz; 1 min
- Test voltage (input/service interface): 3 kVAC; 60 Hz; 1 min
- Test voltage (relay output/service interface): 4 kVAC; 60 Hz; 1 min
- Test voltage (supply/service interface): 2.5 kVAC; 60 Hz; 1 min
- Overvoltage category: II
- Pollution degree: 2
- Insulation type (input, supply and service interface/relay output): Reinforced insulation (safe isolation)
- Insulation type (input/supply/service interface): Basic insulation
- Connection Data — Connection technology: Push-in CAGE CLAMP®
- Connection Data — WAGO connector: picoMAX® 5.0
- Connection Data — Solid conductor: 0.2 … 2.5 mm² / 24 … 12 AWG
- Connection Data — Fine-stranded conductor: 0.2 … 2.5 mm² / 24 … 12 AWG
- Connection Data — Strip length: 9 … 10 mm / 0.35 … 0.39 inches
- Width: 12.5 mm / 0.492 inches
- Height: 110 mm / 4.331 inches
- Depth from upper-edge of DIN-rail: 107 mm / 4.213 inches
- Mounting type: DIN-35 rail
- Weight: 86.6 g
- Ambient temperature (operation): -40 … +70 °C
- Ambient temperature (storage): -40 … +85 °C
- Temperature range of connection cable: ≥ (Tambient + 10 K)
- Temperature range of the connection cable (UL): 80 °C
- Conformity marking: CE
- EMC immunity to interference: EN 61000-6-2; EN 61326-2-3; EN 50121-3-2
- EMC emission of interference: EN 61000-6-4; EN 61326-2-3; EN 50121-3-2
- Standards/specifications: EN 61010-1; EN 61373; EN 50121-3-2
Image shown is representative. Refer to the product specifications for the exact configuration.