Description
The WAGO 2206-8034 distribution terminal block features with push-button, 1 x 6 mm² / 6 x 1.5 mm², with integrated end plate, for Ex e II and Ex i applications, side and center marking, for DIN-rail 35 x 15 and 35 x 7.5, Push-in CAGE CLAMP®, 6,00 mm², blue.
Specifications
- IEC Approvals — Ratings per: IEC/EN 60664-1
- IEC Approvals — Rated voltage (III / 3): 800 V
- IEC Approvals — Rated impulse withstand voltage (III / 3): 8 kV
- IEC Approvals — Rated current: 41 A
- IEC Approvals — Current at conductor cross-section (max.) mm²: 57 A
- IEC Approvals — Legend (ratings): (III / 3) ≙ Overvoltage category III / Pollution degree 3
- Power loss, per pole (potential): 1.311 W
- Rated current IN for power loss specification: 41 A
- Resistance value for specified, current-dependent power loss: 0.001 Ω
- General information — Wiring direction: Front-entry wiring
- Connection Data — Clamping units: 7
- Connection Data — Total number of potentials: 1
- Connection Data — Number of levels: 1
- Connection 1 — Connection type: Input
- Connection 1 — Connection technology: Push-in CAGE CLAMP®
- Connection 1 — Total number of connection points: 1
- Connection 1 — Actuation Method: Push-button
- Connection 1 — Connectable conductor materials: Copper
- Connection 1 — Nominal cross-section: 6 mm²
- Connection 1 — Solid conductor: 0.5 … 10 mm² / 20 … 8 AWG
- Connection 1 — Solid conductor; push-in termination: 2.5 … 10 mm² / 14 … 8 AWG
- Connection 1 — Fine-stranded conductor: 0.5 … 10 mm² / 20 … 8 AWG
- Connection 1 — Fine-stranded conductor; with insulated ferrule: 0.5 … 6 mm² / 20 … 10 AWG
- Connection 1 — Fine-stranded conductor; with ferrule; push-in termination: 2.5 … 6 mm² / 16 … 10 AWG
- Connection 1 — Note (conductor cross-section): Depending on the conductor characteristic, a conductor with a smaller cross-section can also be inserted via push-in termination.
- Connection 1 — Strip length: 13 … 15 mm / 0.51 … 0.59 inches
- Connection 1 — Wiring direction: Front-entry wiring
- Connection 2 — Connection type: Output
- Connection 2 — Connection technology: Push-in CAGE CLAMP®
- Connection 2 — Number of connection points: 6
- Connection 2 — Nominal cross-section: 1.5 mm²
- Connection 2 — Solid conductor: 0.25 … 2.5 mm² / 22 … 14 AWG
- Connection 2 — Solid conductor, push-in termination: 0.75 … 2.5 mm² / 18 … 14 AWG
- Connection 2 — Fine-stranded conductor: 0.25 … 2.5 mm² / 22 … 14 AWG
- Connection 2 — Fine-stranded conductor; with insulated ferrule: 0.25 … 1.5 mm² / 22 … 16 AWG
- Connection 2 — Fine-stranded conductor; with ferrule; push-in termination: 0.75 … 1.5 mm² / 18 … 16 AWG
- Connection 2 — Strip length: 9 … 11 mm / 0.35 … 0.43 inches
- Width: 9 mm / 0.354 inches
- Height: 73.8 mm / 2.905 inches
- Depth from upper-edge of DIN-rail: 32.9 mm / 1.295 inches
- Mounting type: DIN-35 rail
- Marking level: Center/side marking
- Color: blue
- Insulation material (main housing): Polyamide (PA66)
- Flammability class per UL94: V0
- Actuator color: orange
- Weight: 16.3 g
- Processing temperature: -35 … +85 °C
- Continuous operating temperature: -60 … +105 °C
- Test specification: ; Railway applications –; Rolling stock –; Electronic equipment: DIN EN 50155 (VDE 0115-200):2022-06
- Test procedure: ; Railway applications – ; Rolling stock equipment – ; Vibration and shock tests: DIN EN 61373 (VDE 0115-0106):2011-04
- Spectrum/Mounting location: Service life test, Category 1, Class A/B
- Functional test with noise-like oscillations: Test passed according to Section 8 of the standard
- Frequency: f1 = 5 Hz to f2 = 150 Hz
- Acceleration: 0.101g (highest test level used for all axes)
- Test duration per axis: 10 min.
- Test directions: X, Y and Z axes
- Monitoring of contact faults and interruptions: Passed
- Voltage drop measurement before and after each axis: Passed
- Simulated service life test through increased levels of noise-like oscillations: Test passed according to Section 9 of the standard
- Acceleration: 0.572g (highest test level used for all axes)
- Test duration per axis: 5 h
- Extended testing: Monitoring of contact faults and interruptions: Passed
- Extended testing: Voltage drop measurement before and after each axis: Passed
- Shock test: Test passed according to Section 10 of the standard
- Shock pulse form: Half sine
- Acceleration: 5g (highest test level used for all axes)
- Shock duration: 30 ms
- Number of shocks (per axis): 3 pos. und 3 neg.
- Vibration and shock stress for rolling stock equipment: Passed
Image shown is representative. Refer to the product specifications for the exact configuration.