Description
The WAGO 2006-1611 TOPJOB® S tOPJOB®S fuse disconnect terminal block features with pivoting fuse holder for 5 x 20 mm fuse, rail mount, 2-conductor, 7.5 mm wide, gray.
Specifications
- IEC Approvals — Ratings per: IEC/EN 60947-7-3
- IEC Approvals — Rated voltage (III / 3): 800V
- IEC Approvals — Rated impulse withstand voltage (III / 3): 8kV
- IEC Approvals — Rated current: 10A
- IEC Approvals — Legend (ratings): (III / 3) ≙ Overvoltage category III / Pollution degree 3
- Ratings per IEC/EN – Notes — Ratings (note): Electrical ratings are given by the fuse.
- UL Approvals — Approvals per: UL 1059
- UL Approvals — Rated voltage UL (Use Group B): 600V
- UL Approvals — Rated current UL (Use Group B): 15A
- UL Approvals — Rated voltage UL (Use Group C): 600V
- UL Approvals — Rated current UL (Use Group C): 15A
- Approvals per: CSA 22.2 No 158
- Rated voltage CSA (Use Group B): 600V
- Rated current CSA (Use Group B): 15A
- Rated voltage CSA (Use Group C): 600V
- Rated current CSA (Use Group C): 15A
- Power loss Ploss (max.) (note): When selecting glass cartridge fuses, make sure that the maximum power loss listed below is not exceeded. The power loss is determined according to IEC or EN 60947-7-3/VDE 0611-6 at 23°C. The temperature rise of the terminal block must be checked according to their application and mounting. Higher ambient temperatures represent an additional impact on miniature fuses. Therefore, in such applications, the rated current must be reduced if necessary. More details are available from the manufacturers.
- Maximum power loss Ploss of fuse insert for overload and short-circuit protection (individual arrangement): 1.6W
- Maximum power loss Ploss of fuse insert for overload and short-circuit protection (block arrangement): 1.6W
- Maximum power loss Ploss of fuse insert for short-circuit protection (individual arrangement): 2.5W
- Power loss Ploss (max.) of fuse cartridge for short-circuit protection (block arrangement): 2.5W
- General information — Fuse receptacle: pivoting
- General information — Fuse type: Cylindrical fuse; 5 x 20 mm
- General information — Wiring direction: Front-entry wiring
- Connection Data — Clamping units: 2
- Connection Data — Total number of potentials: 1
- Connection Data — Number of levels: 1
- Connection Data — Number of jumper slots: 2
- Connection 1 — Connection technology: Push-in CAGE CLAMP®
- Connection 1 — Actuation Method: Operating tool
- Connection 1 — Connectable conductor materials: Copper
- Connection 1 — Nominal cross-section: 6 mm²
- Connection 1 — Solid conductor: 0.5 … 10 mm² / 20 … 8 AWG
- Connection 1 — Solid conductor; push-in termination: 2.5 … 10 mm² / 14 … 8 AWG
- Connection 1 — Fine-stranded conductor: 0.5 … 10 mm² / 20 … 8 AWG
- Connection 1 — Fine-stranded conductor; with insulated ferrule: 0.5 … 6 mm² / 20 … 10 AWG
- Connection 1 — Fine-stranded conductor; with ferrule; push-in termination: 2.5 … 6 mm² / 16 … 10 AWG
- Connection 1 — Note (conductor cross-section): Depending on the conductor characteristic, a conductor with a smaller cross-section can also be inserted via push-in termination.
- Connection 1 — Strip length: 13 … 15 mm / 0.51 … 0.59 inches
- Connection 1 — Wiring direction: Front-entry wiring
- Width: 7.5 mm / 0.295 inches
- Height: 96.3 mm / 3.791 inches
- Depth from upper-edge of DIN-rail: 59 mm / 2.323 inches
- Mounting type: DIN-35 rail
- Marking level: Center/side marking
- Color: gray
- Insulation material (main housing): Polyamide (PA66)
- Flammability class per UL94: V0
- Weight: 24.9g
- Processing temperature: -35 … +85 °C
- Continuous operating temperature: -60 … +105 °C
- Test specification: ; Railway applications –; Rolling stock –; Electronic equipment: DIN EN 50155 (VDE 0115-200):2022-06
- Test procedure: ; Railway applications – ; Rolling stock equipment – ; Vibration and shock tests: DIN EN 61373 (VDE 0115-0106):2011-04
- Spectrum/Mounting location: Service life test, Category 1, Class A/B
- Functional test with noise-like oscillations: Test passed according to Section 8 of the standard
- Frequency: f1 = 5 Hz to f2 = 150 Hz
- Acceleration: 0.101g (highest test level used for all axes)
- Test duration per axis: 10 min.
- Test directions: X, Y and Z axes
- Monitoring of contact faults and interruptions: Passed
- Voltage drop measurement before and after each axis: Passed
- Simulated service life test through increased levels of noise-like oscillations: Test passed according to Section 9 of the standard
- Acceleration: 0.572g (highest test level used for all axes)
- Test duration per axis: 5 h
- Extended testing: Monitoring of contact faults and interruptions: Passed
- Extended testing: Voltage drop measurement before and after each axis: Passed
- Shock test: Test passed according to Section 10 of the standard
- Shock pulse form: Half sine
- Acceleration: 5g (highest test level used for all axes)
- Shock duration: 30 ms
- Number of shocks (per axis): 3 pos. und 3 neg.
- Vibration and shock stress for rolling stock equipment: Passed