Product Overview

Overview

The PDUMH32HVAT 7.7kW Single-Phase 200-240V Metered Automatic Transfer Switch / ATS PDU provides power monitoring and enables redundant power for network devices with non-redundant power supply configurations. Ideal for data centers and server rooms, it mounts in 2U of space in EIA-standard 19-inch racks and features 18 outlets (16 C13 and two C19) in two load banks, each bank protected by a 20A circuit breaker.
Dual three-meter input cords with IEC 309 32A Blue (2P+E) plugs connect to separate primary and secondary single-phase 200-240V power sources. The PDU constantly evaluates the power quality of both input sources. Dynamic solid-state (TRIAC) automatic transfer switching allows the PDU to switch to the secondary source within 1–5 milliseconds should the primary source fail or become unstable to ensure your connected equipment operates without interruption.
Multifunction digital display with LED indicators reports output current, voltage and kW loading information.

Features

Primary and Secondary Inputs for Power Redundancy
  • Provides power monitoring and enables redundant power for network devices with non-redundant power supply configurations
  • Dual 3m input cords with IEC 309 32A Blue (2P+E) plugs connect to separate primary and secondary single-phase power sources
Automatic Transfer Switching
  • Dynamic solid-state (TRIAC) automatic transfer switching
  • Switches to secondary power source if primary source fails or becomes unstable
  • 1–5 ms transfer time ensures uninterrupted operation of connected equipment
  • Built-in processor monitors both sources and prevents switching if secondary source is unavailable or of lower quality than primary source
Multifunction Digital Display
  • Front-panel digital display with LED indicators reports output current, voltage and kW loading information
20A Circuit Breakers
  • Protect each of 2 single-phase output banks
  • Front-panel LED indicates when breaker has tripped
Cord Retention Sleeves
  • Set of Plug-lock output power cable retention sleeves prevent accidental disconnection of connected devices
Mounts Horizontally in 2U of Rack Space
  • Compatible with EIA-standard 19 in. 4-post racks and rack enclosures
TAA-Compliant
  • Compliant with the Federal Trade Agreements Act (TAA) for GSA Schedule purchases

Package Includes

  • PDUMH32HVAT 7.7kW Single-Phase 200-240V ATS/Metered PDU
  • Rack-mounting brackets
  • Plug-lock cable retention sleeves
  • Cable ties
  • Owner’s manual
TAA compliant RoHS compliant

Specifications

OVERVIEW
UPC Code 037332186881
PDU Type Metered; Auto-Transfer Switch
INPUT
PDU Input Voltage 200-240V DUAL INPUT
Recommended Electrical Service Two single-phase 32A 200-240V circuits
Maximum Input Amps 32
PDU Plug Type (2) IEC-309 32A BLUE (2P+E)
Input Phase Single-Phase
Input Cord Details Set of two inputs connect to separate PRIMARY and SECONDARY power sources
Input Cord Length (ft.) 10
OUTPUT
Output Capacity Details 7.7kW (240V), 7.4kW (230V), 7.0kW (220V), 6.7kW (208), 6.4kW (200V) total capacity; 32A maximum; 16A max per breakered outlet bank; 16A max per C19 outlet; 10A max per C13 outlet
Frequency Compatibility 50 / 60 Hz
Output Receptacles (16) C13; (2) C19
Output Nominal Voltage 200-240V
Overload Protection Includes two 20A output circuit breakers; Breaker 1 controls the upper row of 9 outlets (8 C13, 1 C19); Breaker 2 controls the lower row of outlets (8 C13, 1 C19)
USER INTERFACE, ALERTS & CONTROLS
Front Panel LCD Display Digital display reports output amps in 4 separately metered loading segments (BANK 1: Outlets #1-9; BANK 2: Outlets #10-18), whole-PDU output kW load level and input voltage on primary and secondary input lines
Front Panel LEDs Front panel LEDs confirm amp / kilowatt / voltage reporting information
Switches ENTER and MODE switches toggle the digital display to show output amps (Banks 1-4), total kW output and input voltage (primary, secondary)
PHYSICAL
Material of Construction Metal
Form Factors Supported 2U rackmount
Minimum Required Rack Depth (inches) 16
PDU Form Factor Horizontal (2U)
Shipping Dimensions (hwd / in.) 7.70 x 16.70 x 19.30
Shipping Weight (lbs.) 20.30
Unit Dimensions (hwd / in.) 3.5 x 17.5 x 12.5
Unit Weight (lbs.) 13.7
ENVIRONMENTAL
Operating Temperature Range 0C ~ 40C (32F ~ 104F)
Storage Temperature Range -30°C to +50°C (-22°F to +122°F)
Relative Humidity 5 to 95% (non-condensing)
Operating Elevation (ft.) 0-10,000
Operating Elevation (m) 0-3000
STANDARDS & COMPLIANCE
Certifications Tested to CE / IEC 60950-1, EN CLASS A (Emissions), NOM (Mexico), RoHS Compliant, TAA Compliant
WARRANTY
Product Warranty Period (Worldwide) 2-year limited warranty

Overview

The PDUMH32HVAT 7.7kW Single-Phase 200-240V Metered Automatic Transfer Switch / ATS PDU provides power monitoring and enables redundant power for network devices with non-redundant power supply configurations. Ideal for data centers and server rooms, it mounts in 2U of space in EIA-standard 19-inch racks and features 18 outlets (16 C13 and two C19) in two load banks, each bank protected by a 20A circuit breaker.
Dual three-meter input cords with IEC 309 32A Blue (2P+E) plugs connect to separate primary and secondary single-phase 200-240V power sources. The PDU constantly evaluates the power quality of both input sources. Dynamic solid-state (TRIAC) automatic transfer switching allows the PDU to switch to the secondary source within 1–5 milliseconds should the primary source fail or become unstable to ensure your connected equipment operates without interruption.
Multifunction digital display with LED indicators reports output current, voltage and kW loading information.

Features

Primary and Secondary Inputs for Power Redundancy
  • Provides power monitoring and enables redundant power for network devices with non-redundant power supply configurations
  • Dual 3m input cords with IEC 309 32A Blue (2P+E) plugs connect to separate primary and secondary single-phase power sources
Automatic Transfer Switching
  • Dynamic solid-state (TRIAC) automatic transfer switching
  • Switches to secondary power source if primary source fails or becomes unstable
  • 1–5 ms transfer time ensures uninterrupted operation of connected equipment
  • Built-in processor monitors both sources and prevents switching if secondary source is unavailable or of lower quality than primary source
Multifunction Digital Display
  • Front-panel digital display with LED indicators reports output current, voltage and kW loading information
20A Circuit Breakers
  • Protect each of 2 single-phase output banks
  • Front-panel LED indicates when breaker has tripped
Cord Retention Sleeves
  • Set of Plug-lock output power cable retention sleeves prevent accidental disconnection of connected devices
Mounts Horizontally in 2U of Rack Space
  • Compatible with EIA-standard 19 in. 4-post racks and rack enclosures
TAA-Compliant
  • Compliant with the Federal Trade Agreements Act (TAA) for GSA Schedule purchases

Package Includes

  • PDUMH32HVAT 7.7kW Single-Phase 200-240V ATS/Metered PDU
  • Rack-mounting brackets
  • Plug-lock cable retention sleeves
  • Cable ties
  • Owner’s manual
TAA compliant RoHS compliant

Specifications

OVERVIEW
UPC Code 037332186881
PDU Type Metered; Auto-Transfer Switch
INPUT
PDU Input Voltage 200-240V DUAL INPUT
Recommended Electrical Service Two single-phase 32A 200-240V circuits
Maximum Input Amps 32
PDU Plug Type (2) IEC-309 32A BLUE (2P+E)
Input Phase Single-Phase
Input Cord Details Set of two inputs connect to separate PRIMARY and SECONDARY power sources
Input Cord Length (ft.) 10
OUTPUT
Output Capacity Details 7.7kW (240V), 7.4kW (230V), 7.0kW (220V), 6.7kW (208), 6.4kW (200V) total capacity; 32A maximum; 16A max per breakered outlet bank; 16A max per C19 outlet; 10A max per C13 outlet
Frequency Compatibility 50 / 60 Hz
Output Receptacles (16) C13; (2) C19
Output Nominal Voltage 200-240V
Overload Protection Includes two 20A output circuit breakers; Breaker 1 controls the upper row of 9 outlets (8 C13, 1 C19); Breaker 2 controls the lower row of outlets (8 C13, 1 C19)
USER INTERFACE, ALERTS & CONTROLS
Front Panel LCD Display Digital display reports output amps in 4 separately metered loading segments (BANK 1: Outlets #1-9; BANK 2: Outlets #10-18), whole-PDU output kW load level and input voltage on primary and secondary input lines
Front Panel LEDs Front panel LEDs confirm amp / kilowatt / voltage reporting information
Switches ENTER and MODE switches toggle the digital display to show output amps (Banks 1-4), total kW output and input voltage (primary, secondary)
PHYSICAL
Material of Construction Metal
Form Factors Supported 2U rackmount
Minimum Required Rack Depth (inches) 16
PDU Form Factor Horizontal (2U)
Shipping Dimensions (hwd / in.) 7.70 x 16.70 x 19.30
Shipping Weight (lbs.) 20.30
Unit Dimensions (hwd / in.) 3.5 x 17.5 x 12.5
Unit Weight (lbs.) 13.7
ENVIRONMENTAL
Operating Temperature Range 0C ~ 40C (32F ~ 104F)
Storage Temperature Range -30°C to +50°C (-22°F to +122°F)
Relative Humidity 5 to 95% (non-condensing)
Operating Elevation (ft.) 0-10,000
Operating Elevation (m) 0-3000
STANDARDS & COMPLIANCE
Certifications Tested to CE / IEC 60950-1, EN CLASS A (Emissions), NOM (Mexico), RoHS Compliant, TAA Compliant
WARRANTY
Product Warranty Period (Worldwide) 2-year limited warranty