Description

Description of Function

Upon application of control voltage, the time delay is ready to accept a trigger. When the trigger is applied, the time delay (t) begins. At the end of the time delay (t), the output is energized and remains in that condition as long as both the trigger and control voltage remain. If the trigger is removed during the time delay (t), the output remains de-energized & the time delay (t) is reset.

Features

  • Onboard & remote adjustable or fixed time delays from 0.05 seconds to 2 hours
  • Uses industry-standard 8 pin octal sockets
  • 10A DPDT output contacts
  • Pilot Duty Rating

Specifications

  • Function: On Delay (Switch Trigger)
  • CONTROL VOLTAGE: 240V AC
  • Output: 10A DPDT
  • TIMING RANGE: 3 – 300 Sec
  • MOUNT: 11-Pin Socket
  • Setting Adjustment: Analog
  • REMOTE POTENTIOMETER: Consult Factory
  • Enclosure Style: Plug-in
  • Configuration / Contact Rating: DPDT 10A @ 240V AC / 10A @ 30V DC, 1/2HP @ 120/240V AC (N.O.), 1/3HP @ 120/240V AC (N.C.), B300 & R300
  • Approvals: UL Recognized for the U.S. and Canada, CE
  • AC Operation: +10/-15% of nominal at 50/60 Hz
  • Load (Burden): 2 VA
  • Setting Accuracy: Maximum Setting (Adjustable): +5%, -0%
  • Setting Accuracy: Minimum Setting (Adjustable): +0%, -50%
  • Fixed: ±2% or 50ms, whichever is greater
  • Repeat Accuracy: ±0.1% or ±0.04 seconds, whichever is greater
  • Reset Time: 0.04 Seconds
  • Start-up Time: 0.05 Seconds
  • Maintain Function Time: 0.01 Seconds
  • Temperature: Operating: -28° to 65° C (-18° to 149° F)
  • Temperature: Storage: -40° to 85° C (-40° to 185° F)
  • Life: Mechanical: 10,000,000 operations
  • Life: Full Load: 100,000 operations