Description
Description of Function
Upon application of control voltage, the output is energized and the time delay (t) begins. At the end of the time delay (t), the output is de-energized and remains in that condition for the time delay (t). At the end of the time delay (t), the output is energized and the sequence repeats until the control voltage is removed.
Features
- Cost effective design & compact 2″ x 2″ enclosure are ideal for volume OEM applications
- Microprocessor-based design for greater performance & maximum flexibility
- Encapsulated for protection against harsh environments
- 10A SPDT relay output contacts
- Relay common internally connected to pin 2 for easier wiring
- Onboard, adjustable, or fixed time delays from 0.05 seconds to 100 hours
Specifications
- Function: Flasher (ON 1st)
- CONTROL VOLTAGE: 120V AC/DC
- Output: 10A SPDT
- TIMING RANGE: 10 – 1,000 Min
- MOUNT: Single Screw Mounting
- Setting Adjustment: Analog
- Options: Control Voltage connected at Relay Common
- REMOTE POTENTIOMETER: Consult Factory
- Enclosure Style: Encapsulated
- Configuration / Contact Rating: SPDT 10A @ 240V AC / 7A @ 28V SPDT, 1/4 HP @ 120V AC (N.O.)
- Approvals: UL Recognized for the U.S. and Canada, CE
- AC Operation: +10/-15% of nominal at 50/60 Hz
- DC Operation: +10/-15% of nominal
- Load (Burden): 2 VA
- Setting Accuracy: Maximum Setting (Adjustable): +5%, -0%
- Setting Accuracy: Minimum Setting (Adjustable): +0%, -50%
- Fixed: ±2% or ±50ms, whichever is greater
- Repeat Accuracy: ±0.1% or ±0.04 seconds, whichever is greater
- Reset Time: 0.1 Seconds
- Start-up Time: 0.05 seconds
- Maintain Function Time: 0.01 seconds
- Temperature: Operating: -28° to 65° C (-18° to 149° F)
- Temperature: Storage: -40° to 85° C (-40° to 185° F)
- Life: Mechanical: 10,000,000 operations
- Life: Full Load: 100,000 operations
- Mounting: Surface with one #8 or #10 screw and a maximum tightening torque of 15 in-lbs
- Termination: 0.25″ male quick-connect terminals
Resources