Description
Description of Function
Upon application of control voltage, the time delay relay is ready to accept a trigger. When the trigger is applied, the output remains de-energized. Upon removal of the trigger, the output is energized and the time delay (t) begins. At the end of the time delay (t), the output is de-energized unless the trigger is removed and re-applied prior to time out (before time delay (t) elapses). Continuous cycling of the trigger at a rate faster than the time delay (t) will cause the output to remain energized indefinitely.
Features
- DIP-Switches for accurate digital set of time delay
- Uses Industry-standard 11 pin sockets
- 10A DPDT output contacts
- LED indicates relay status
- Pilot Duty Rating
Specifications
- Function: Single Shot Falling Edge
- CONTROL VOLTAGE: 240V AC
- Output: 10A DPDT
- TIMING RANGE: 10 – 10,230 Sec
- MOUNT: 11-Pin Socket
- Setting Adjustment: Digital
- Enclosure Style: Plug-in
- Configuration / Contact Rating: DPDT 10A @ 240V AC / 10A @ 30V DC, 1/2HP @ 120/240V AC (N.O.), 1/3HP @ 120/240V AC (N.C.), B300 & R300
- Approvals: UL Recognized for the U.S. and Canada, CE
- AC Operation: +10/-15% of nominal at 50/60 Hz
- Load (Burden): 2 VA
- Constant Voltage & Temperature: ±0.1% of set time or ±50ms, whichever is greater
- Variable Voltage & Temperature: ±1% of set time or ±50ms, whichever is greater
- Constant Voltage & Temperature: ±0.1% of set time or ±0.02 seconds, whichever is greater
- Variable Voltage & Temperature: ±1% of set time or ±0.02 seconds, whichever is greater
- Reset Time: 0.04 Seconds
- Start-up Time: 0.05 Seconds
- Maintain Function Time: 0.01 Seconds
- Insulation Voltage: 2kV
- Operation: -28° to 65° C (-18° to 149° F)
- Storage: -40° to 85° C (-40° to 185° F)
- Life: Mechanical: 10,000,000 operations
- Life: Full Load: 100,000 operations