Description
Description of Function
Upon application of control voltage, the time delay (t) begins. At the end of the time delay (t), the output is energized and remains in that condition for the time delay (t). At the end of the time delay (t), the output is de-energized and the sequence repeats until the control voltage is removed.
Features
- Pushbutton thumbwheels for digital set of time delay
- 50ms – 999 hour programmable time range
- Uses industry-standard 8 pin octal sockets
- 10A DPDT output contacts
- LED indicates timing mode and time out conditions
- Pilot Duty Rating
Specifications
- Function: Flasher (OFF 1st)
- CONTROL VOLTAGE: 120V AC/DC
- Output: 10A DPDT
- TIMING RANGE: 0.05 Sec – 999 Hrs
- MOUNT: 8-Pin Socket
- Setting Adjustment: Digital
- Enclosure Style: Plug-In
- Configuration / Contact Rating: DPDT 10A @ 240V AC / 10A @ 30V DC, 1/2HP @ 120/240V AC (N.O.), 1/3HP @ 120/240V AC (N.C.), B300 & R300
- Approvals: UL Recognized for the U.S. and Canada, CE
- AC Operation: +10/-15% of nominal at 50/60 Hz
- DC Operation: +10/-15% of nominal
- Load (Burden): 3 VA
- Constant Voltage & Temperature: ±0.1% of set time or ±50ms, whichever is greater
- Variable Voltage & Temperature: ±1% of set time or ±50ms, whichever is greater
- Constant Voltage & Temperature: ±0.1% of set time or ±0.02 seconds, whichever is greater
- Variable Voltage & Temperature: ±1% of set time or ±0.02 seconds, whichever is greater
- Reset Time: 0.1 Seconds
- Start-up Time: 0.05 Seconds
- Maintain Function Time: 0.01 Seconds
- Temperature: Operating: -28° to 65° C (-18° to 149° F)
- Temperature: Storage: -40° to 85° C (-40° to 185° F)
- Insulation Voltage: 2 kV
- Life: Mechanical: 10,000,000 operations
- Life: Full Load: 100,000 operations
Resources