Description
Description of Function
Upon application of control voltage, output is energized and the time delay (t) begins. At the end of the time delay (t), the output is de-energized. Control voltage must be removed to reset the time delay relay.
Features
- Pushbutton thumbwheels for digital set of time delay
- 50ms – 999 hour programmable time range
- Uses industry-standard 8 pin octal sockets
- 10A DPDT output contacts
- LED indicates timing mode and time out conditions
- Pilot Duty Rating
Specifications
- Function: Interval On
- CONTROL VOLTAGE: 12V DC
- Output: 10A DPDT
- TIMING RANGE: 0.05 Sec – 999 Hrs
- MOUNT: 8-Pin Socket
- Setting Adjustment: Digital
- Enclosure Style: Plug-In
- Configuration / Contact Rating: DPDT 10A @ 240V AC / 10A @ 30V DC, 1/2HP @ 120/240V AC (N.O.), 1/3HP @ 120/240V AC (N.C.), B300 & R300
- Approvals: UL Recognized for the U.S. and Canada, CE
- DC Operation: +10/-15% of nominal
- Load (Burden): 3 VA
- Constant Voltage & Temperature: ±0.1% of set time or ±50ms, whichever is greater
- Variable Voltage & Temperature: ±1% of set time or ±50ms, whichever is greater
- Constant Voltage & Temperature: ±0.1% of set time or ±0.02 seconds, whichever is greater
- Variable Voltage & Temperature: ±1% of set time or ±0.02 seconds, whichever is greater
- Reset Time: 0.1 Seconds
- Start-up Time: 0.05 Seconds
- Maintain Function Time: 0.01 Seconds
- Temperature: Operating: -28° to 65° C (-18° to 149° F)
- Temperature: Storage: -40° to 85° C (-40° to 185° F)
- Insulation Voltage: 2 kV
- Life: Mechanical: 10,000,000 operations
- Life: Full Load: 100,000 operations
Resources