Belden 89841 002500 RS485, 1 Pr #24 Str TC, FEP Ins, OS+TC Brd, FEP Jkt, CMP - Red

$4,824.99
SKU:
89841 002500
Shipping:
Calculated at Checkout
Color:
Red
Manufacturer Status:
Active
Product Family:
89841
In Stock
Available
Before Ordering

Availability and lead times may vary. Request a quote if you need to confirm availability before placing your order.

Family Owned Since 1932
Nationwide Shipping Serving all 50 states
Technical Support Product selection assistance
Project Assistance Quotes and sourcing support

Description

Belden 89841 002500 RS485, 1 Pr #24 Str TC, FEP Ins, OS+TC Brd, FEP Jkt, CMP

RS-485, 1 Pair 24AWG (7x32) Tinned Copper, FEP Insulation, Overall Beldfoil®+Tinned Copper Braid(90%) Shield, FEP Outer Jacket, CMP

Ordering Details

  • Manufacturer Part Number: 89841 002500
  • Color: Red
  • UPC/EAN: 612825221319

Product Overview

  • Suitable Applications: RS-485, POS; Computer communications; Low Voltage Analog Signals (4-20ma, 0-10v, ...); Low Voltage Digital Control (24v, …); Line Level Audio; Panel Wiring; serial communication (RS-485 standard) comprising of PLCs, VFDs, HMIs, motors, RTU, SCADA, etc. within noisy environments over long distance, etc.

Construction Details

  • Element: Pair(s); No. of Elements: 1; Size: 24 AWG; Stranding: 7x32; Material: TC - Tinned Copper
  • Element: Pair(s); Material: FEP - Fluorinated Ethylene Propylene (Foam); Nom. Thickness: 0.025 in (0.64 mm); Nom. Insulation Diameter: 0.074 in (1.9 mm); Color Code: White/Blue Stripe & Blue/White Stripe
  • Shield Type: Tape; Material: Bi-Laminate (Alum+Poly); Coverage: 100%; Drainwire Type: 24 AWG (7x32) TC
  • Shield Type: Braid; Material: Tinned Copper (TC); Coverage: 90%
  • Material: FEP - Fluorinated Ethylene Propylene; Nom. Thickness: 0.015 in (0.38 mm); Nom. Diameter: 0.204 in (5.18 mm)
  • Overall Cable Diameter (Nominal): 0.204 in (5.18 mm)

Electrical Characteristics

  • Element: Pair(s); Nom. Conductor DCR: 24 Ohm/1000ft; Nom. Capacitance Cond-to-Cond: 12 pF/ft (39 pF/m); Nom. Capacitance Cond-to-Other (Conds + Shield): 22 pF/ft (72 pF/m); Nom. Characteristic Impedence: 120 Ohm; Nom. Velocity of Prop.: 76%; Max. Current: 4 Amps per Conductor at 25ºC
  • Nom Outer Shield DCR: 3.1 Ohm/1000ft (10 Ohm/km)
  • Element: Pair(s); Frequency [MHz]: 1; Nom. Insertion Loss (Attenuation): 0.6 dB/100ft
  • UL Voltage Rating: 300 V (CMP)

Mechanical Characteristics

  • UL Temperature: 200°C; Operating: -70°C to +200°C
  • Stationary Min.: 2.25 in (57.2 mm); Installation Min.: 2.25 in (57.2 mm)
  • Max. Pull Tension: 45.7 lbs (20.7 kg)
  • Bulk Cable Weight: 27 lbs/1000ft

Standards and Compliance

  • Environmental Suitability: Indoor, Oil Resistance
  • Flammability / Reaction to Fire: NFPA 262, UL 910 (Plenum), FT6, IEC 60332-1-2
  • CPR Compliance: CPR Euroclass: Eca
  • NEC / UL Compliance: Article 800, CMP
  • CEC / C(UL) Compliance: CMP
  • European Directive Compliance: EU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), REACH, EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)
  • UK Regulation Compliance: UKCA Mark
  • APAC Compliance: China RoHS II (GB/T 26572-2011)
  • Non-Plenum Number: 9841, 9841ZH

Product Notes

  • Notes: Oil and Gas Resistant

History

  • Update and Revision: Revision Number: 0.578 Revision Date: 02-20-2026