Description
Belden 6120UL 002500 Fire Alarm, #14-2c BC, FPLP
Fire Alarm Cable, Plenum-FPLP, 2-14 AWG solid bare copper conductors with Flamarrest® insulation, Flamarrest® jacket with ripcord
Ordering Details
- Manufacturer Part Number: 6120UL 002500
- Color: Red
- UPC/EAN: 612825173724
Image is for illustration only. Actual cable color and packaging may vary. Refer to the listed color, length, and put-up for this part number.
Product Overview
- Suitable Applications: Fire Alarm, Monitor/Detection, Circuits: Audio, Control, Initiating, Notification
Construction Details
- Element: Conductor(s); No. of Elements: 2; Size: 14 AWG; Stranding: Solid; Material: BC - Bare Copper
- Element: Conductor(s); Material: PVC - Polyvinyl Chloride; Nom. Thickness: 0.010 in (0.25 mm); Nom. Insulation Diameter: 0.0845 in (2.15 mm); Color Code: Black, Red
- Material: PVC - Polyvinyl Chloride; Nom. Thickness: 0.015 in (0.38 mm); Nom. Diameter: 0.201 in (5.11 mm); Ripcord: Yes
- Overall Cable Diameter (Nominal): 0.201 in (5.11 mm)
Electrical Characteristics
- Element: Conductor(s); Nom. Conductor DCR: 2.42 Ohm/1000ft; Nom. Capacitance Cond-to-Cond: 37 pF/ft (120 pF/m); Max. Current: 25 Amps per conductor @ 25°C
- UL Voltage Rating: 300 V
Mechanical Characteristics
- UL Temperature: 75°C; Operating: 0°C to +75°C
- Stationary Min.: 1.6 in (41 mm); Installation Min.: 1.6 in (41 mm)
- Max. Pull Tension: 99.4 lbs (45.1 kg)
- Bulk Cable Weight: 34 lbs/1000ft
Standards and Compliance
- Environmental Suitability: Indoor - Plenum, Indoor
- Flammability / Reaction to Fire: NFPA 262, UL 910 (Plenum)
- NEC / UL Compliance: Article 760, FPLP
- European Directive Compliance: EU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)
- APAC Compliance: China RoHS II (GB/T 26572-2011)
- Other Standard Compliance(s): California State Fire Marshall
- Non-Plenum Number: 5120UL
History
- Update and Revision: Revision Number: 0.440 Revision Date: 09-07-2025
- Footnote: C - CRATE REEL PUT-UP.
Resources
- Technical Data Sheet
- Safe-T-Line Product Bulletin
- Fire Alarm Cable Product Bulletin
- Armored Power-Limited Fire Alarm FPLP
- Sound, Security & Alarm Cable Selection Overview
- Access Control Composite Cables
- NewGen Cables Product Bulletin
- Belden Low Capacitance Digital Fire Alarm Cables
- Waterdog Cables Product Bulletin
- RoHS Compliance Declaration