Description
Belden 1337A 00310000 Fieldbus, 1 Pr #18 Str TC, PO Ins, IS/OS, 1C #18 Str PVC Ins, PVC Jkt, 600V TC-ER
Fieldbus, 1 Pair 18AWG (7x26) Tinned Copper, PO Insulation, Individual & Overall Beldfoil® Shield, 1 Conductor 18AWG (7x26) Tinned Copper, PVC Insulation, Orange PVC Outer Jacket, 600V TC-ER
Ordering Details
- Manufacturer Part Number: 1337A 00310000
- Color: Orange
- UPC/EAN: 612825112266
Image is for illustration only. Actual cable color and packaging may vary. Refer to the listed color, length, and put-up for this part number.
Product Overview
- Suitable Applications: harsh environment digital and serial two-way communication, oil and gas extraction and refining sites, petrochemical, Profibus process automation or Foundation FieldBus process automation, extreme temperature environments, exposure to humidity/moisture, dust, and oil, remote locations long distance applications, etc.
Construction Details
- Element: Pair(s); Size: 18 AWG; Stranding: 7x26; Material: TC - Tinned Copper
- Element: Conductor(s); Material: PP - Polypropylene; Color Code: Blue & Orange
- Element: Ground; Material: PVC - Polyvinyl Chloride; Color Code: Green/Yellow; Notes: Flame Retardant
- Element: Data Pair(s)
- Material: Bi-Laminate (Alum+Poly)
- Material: PVC - Polyvinyl Chloride; Nom. Thickness: 0.060 in (1.5 mm); Nom. Diameter: 0.362 in (9.19 mm)
Electrical Characteristics
- Nom. Conductor DCR: 7.06 Ohm/1000ft (23.2 Ohm/km); Nom. Characteristic Impedence: 100 Ohm; Nom. Inductance: 0.22 µH/ft (0.72 µH/m); Max. Current: 5 Amps per Conductor
- Nom Outer Shield DCR: 1.51 Ohm/1000ft (4.95 Ohm/km)
- UL Voltage Rating: 600 V
Mechanical Characteristics
- UL Temperature: 75°C; Operating: -30°C to +75°C
- Stationary Min.: 3.62 in (91.9 mm); Installation Min.: 3.62 in (91.9 mm)
- Max. Pull Tension: 44.8 lbs (20.3 kg)
- Bulk Cable Weight: 68 lbs/1000ft (100 kg/km)
Standards and Compliance
- Environmental Suitability: Outdoor, Sunlight Resistance, UV Resistance, Oil Resistance
- Flammability / Reaction to Fire: UL1685 UL Loading
- NEC / UL Compliance: Article 725, TC-ER
History
- Update and Revision: Revision Number: 0.541 Revision Date: 03-30-2026